![Bentone STG 146/2 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/bentone/stg-146-2/stg-146-2_installation-and-maintenance-instruction_2735603007.webp)
7
Bentone
2.2
Capacity range
Category
Country of destination
Supply pressure
II
2R3R
AT, BE, BG, CH, CY, CZ, DE, DK, EE, ES, FI, FR, GB, GR,
HR, HU, IE, IS, IT, LT, LU, LV, MK, MT, NL, NO, PL, PT, RO,
RS, SE, SI, SK, TR
20 mbar
II
2H3B/P
AT, CH, CY, DK, FI, LT, RO, SE, SK
20 mbar
II
2H3P
GB, IE
20 mbar
II
2L3B/P
NL, RO
20 mbar
II
2E3B/P
PL
20 mbar
I
2E(R)B
BE
20 mbar
I
3P
BE
20 mbar
160302-264-3
2.3
Gas categories, approved gases
Only dry gas is permitted for use.
STG 146/2
G20 41 - 133
4.3
14.1
360
360
360
MBC 120
MB-DLE 405
MB-DLE 407
G25 41 - 133
5.0
16.4
360
360
360
MBC 120
MB-DLE 405
MB-DLE 407
G30 47 - 144
1.5
4.5
200
360
200
360
MBC 65
MBC 120
MB-DLE 403
MB-DLE 405
G31 47 - 144
1.9
5.9
200
360
200
360
MBC 65
MBC 120
MB-DLE 403
MB-DLE 405
160302-263-4
Capacity
kW
Gas quantity at
min. power
Nm
3
/h
Gas quantity at
max. power
Nm
3
/h
Max. connection
pressure
mbar
Min. connection
pressure
mbar
Gas valve
MultiBloc
See data plate.
Gas quantity and capacity vary according to grade of gas and connection pressure.
Measurements according to EN 3746: 2010
Alt.1 The noise level of the burner can be reduced by equipping the burner with
silencer. Installation must be done so it does not prevent air supply to the
burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
2.4
Technical specification
STG 146/2
Main supply
230V, 1~, 0.95A, 50Hz, IP20
Max fuse rating
8A
NO
X
-class
2
Noise level
78dBA