31
Bentone
6.6 Flame monitoring and ionisation
current check
The standard version of the burner is monitored according to the ionisation
principle. The ionisation current should be checked on initial start-up and at
each service visit.
The reason for low ionisation current can be leakage current, poor
connection to earth, fouling or incorrectly positioned ionisation electrode
in the combustion head. Occasionally, an incorrect gas/air mix may result
in poor ionisation current. Ionisation current is measured using a micro
ammeter (µA) connected in series with the ionisation electrode and gas
burner control. Connect the µ ammeter according to the diagram. The
minimum required ionisation current is shown in the table. In practice, this
current must be significantly higher, preferably more than 10 µA. Connection
of the µA instrument is made easier by the fact that all gas burners are
equipped with a divisible ionisation cable.
Technical data
For continuous operation!
Idle voltage at ION-terminals
AC 115-230 V
!
Protect the ionisation electrode from electric shock!
Short-circuit current
Max. AC 100-300 mA
Min. current for flame detection
Min. DC 1.5 µA
Required current to ensure
detection
Min. DC 3 µA
Possible detection current
Max. DC 20 µA
Operational indicator lamp
flashes green
<5 µA DC
Operational indicator lamp
shines green
>5 µA DC
172 615 02 2018-01-02
Содержание STG 120/2
Страница 17: ...17 Bentone 4 9 Gas nozzle Inner assembly Natural LPG Natural gas LPG 2 5 8...
Страница 25: ...25 Bentone Adjustment of inner assembly Air adjustment Control of burner head 0 2 5 0 7 5 STG120 STG146...
Страница 35: ...35 Bentone 172 615 76 2020 10 16 2 9 1 Wiring diagram Gas burner control LME21...
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...