172 425 37 14-01
List of components
A1
Gas burner control
A2
Power control
A3
Valve, leak tester, Dungs VPS504
B1
Ionization electrode
F1
Operation fuse
F2
Operating fuse
F3
Operating fuse
H1
Operating lamp
H2
Lamp, high capacity
K1
Motor contactor with thermal overload protector
K2
Auxiliary relay
M1
Burner motor
M2
Damper motor, L&S SQN75.664.A21B
S1
Operating switch
S3
Control thermostat
S4
Temperature limiter
S5
Micro switch for hinged door
S7
Main switch
S8
Air pressure switch
Function
1. Operating switch ON-Thermostat ON-Gas pressure switch ON-Air damper
closed.
A control is made that the air pressure switch does not indicate fan pressure.
Then the burner motor starts.
2. Air damper motor opens.
The air damper motor opens the damper to max. position. A control is made that
the air pressure switch indicates suficient fan pressure.
3. Air damper motor closes.
The air damper motor closes to min. load position. Then the ignition spark is
formed.
4. Main and safety valves open
The gas is ignited. The ionization electrode indicates a lame.
5. The safety time expires.
The ignition spark goes out. The safety time expires. If there is no lame or if for
some reason the lame disappears after this time limit, the burner control locks
out.
6. Operating position.
The burner is in operating position and can now change over to the capacity
controlled by the regulator.
7. Stop.
The operation of the burner can now be interrupted by means of the operating
switch or the thermostat.
•
The control locks out.
The red lamp in the control is lit. Restart the burner by pressing the reset button.
ELECTRIC EQUIPMENT
Gas burner control: LFL1...
Mains connection and fuse in accordance with local regulations.
S10 Gas pressure switch, max.
S11 Change-over switch, Aut.-man.
S12 Change-over switch, Increase-Reduce
S15 Control thermostat, 3-pole (only for 2-stage sliding)
S20 Main switch
T1
Ignition transformer
X1
Connection terminal board
X2
Earth terminal
X3
Plug-in contact, burner
X4
Plug-in contact, boiler
X15 Plug-in contact, power controller, burner
X16 Plug-in contact, power controller
X7
Plug-in contact, 3 phase, burner
X8
Plug-in contact, 3 phase, boiler
S9
Gas pressure switch
Y1
Gas solenoid valve 1
Y3
Safety solenoid valve
2(2)
Max loading K1
Connection A1,A2 / 95, 96 / 97, 98 Max 0,2A/15W
Содержание BG 800 CN
Страница 2: ......
Страница 6: ...TECHNICAL DATA 172 215 48 07 01 14 280 320 380 206 Dimensions of lange...
Страница 27: ......
Страница 30: ......
Страница 31: ......
Страница 32: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...