Adjustment of outlet pressure
(setpoint adjustment)
Factory setting: Standard spring p 2
10-30 mbar
1.
1.
Unscrew protective cap A.
2.
Adjustment (+) Setting spindle
B ”Turn counter-clockwise”
= Increasing outlet pressure
(setpoint)
or
2.
Adjustment (-) Setting spindle B
”Turn clockwise” = Reducing outlet
pressure (setpoint)
4. Check setpoint
5. Screw on protective cap A.
6. Attach lead seal (Page 5).
4.
B
E
C/D
B
A
3.
Replace setting spring 3-4
1.
Remove protective cap. A.
Release spring by turning
adjustment spindle B counter
clockwise. Turn spindle to
stop.
2.
Unscrew complete adjustment
device B and remove spring C.
3.
Insert new spring D.
4.
Assemble complete
adjustment device and adjust
desired off-set.
5.
Screw on protective cap A.
Stick adhesive label E onto
typeplate.
6.
Attach lead seal.