6
Bentone
Control system
10 years
250 000 starts
Valve control system
10 years
250 000 starts
Pressure switch
10 years
250 000 starts
Ignition system with flame guard
10 years
250 000 starts
UV flame sensor
10 000 hrs
N/A
Gas pressure regulators
15 years
N/A
Gas valve without seal testing
10 years
250 000 starts
Gas valve with seal testing
Replacement upon fault detection
N/A
Gas pressure switch
10 years
250 000 starts
Safety blow-off system
10 years
N/A
Damper motor
N/A
500 000 starts
Contactor
10 years
500 000 starts
Burner
1 year
3 000 hrs
Inspection of electrical installation
1 year
3 000 hrs
Leakage check
1 year
3 000 hrs
Filter
1 year replacement at Δp>10 mbar
3 000 hrs replacement at
Δp>10 mbar
Electrodes
Replacement/Cleaning 1 year
Replacement/Cleaning 3 000 hrs
Brake disc
Replacement/Cleaning 1 year
Replacement/Cleaning 3 000 hrs
Motor
1 year
3 000 hrs
Fan wheel
1 Year
Replacement when cleaning
needed/imbalance
3 000 hrs
Replacement when cleaning
needed/imbalance
The burner and its components must be recycled according to applicable regulations.
Burner servicing schedule
Servicing must be carried out once a year or after 3 000 hours of operation.
Component replacement intervals
Delivery check
• Make sure everything is delivered and the goods have not been
damaged during transit.
• If something is wrong with a delivery, report it to the supplier.
• Transport damage must be reported to the shipping company.
Содержание BFG 1 H1
Страница 13: ...13 Bentone BFG1 4 3 5 1 6 2 10 16 9 15 14 13 7 8 22 11 12 2 7 Description ...
Страница 47: ...47 Bentone BFG1 Alt 1 Acc to DIN 4791 Alt 2 Alt 3 8 2 Wiring diagram ...
Страница 54: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...