9
Bentone
Nozzle:
45° Solid/semisolid
60° Solid/semisolid
80° Solid/semisolid
Pump pressure
10 bar (8-25 bar)
2.6 Burner installation
2.6.1 Hole patten
Make sure the hole pattern on the boiler is designed for burner flange.
Combustion device
d
1
d
2
d
3
B 30
ø 110
M10
ø 160-200
Because of the various boiler types with varying furnace geometries and
furnace loads, it is impossible to commit to a certain scattering angle or a
specific distribution pattern.
It should be noted that the scattering angle and distribution pattern changes
with pump pressure.
d
1
d
2
d
3
2.4 Setting of brake plate and air flow
2.5 Recommended nozzle and
pressure
!
*NB It is important
that the spark does
not strike against the
brake plate or nozzle.
a
b
c
d
B 30
2.5-3.5
7,0-9,0
1.0-2.0
5.0-6.0
a
b
c
d