Ramp Differential Expansion Monitor Maintenance
84414-01
8
Alarm Setpoint Adjust
1. Open front panel.
2. Set switch the Setpoint Adjust switch
(SA) to the left (ON).
3. Select Short rotor setpoints by setting
the Long/Short (US) switch to the right.
The left bargraph will start flashing the
differential expansion signal.
4. To adjust Alert or Danger setpoints,
press a n d h o l d ALERT o r DANGER
switch on the front panel.
5. Use the ( r ) o r (4.) switches on the
System Monitor to adjust the setpoint
level up or down.
6. Repeat for Long setpoints by setting
the Long/Short (US) switch to the left.
7. Reset SA to the right (OFF).
8. Close front panel.
DIFFERENTIAL
EXPANSION IGNITOR
• li t'i) ),1
3 1 0 0 / . 0
F F ERE'
iF .,P,1115
r
1 6
Содержание 3300/46
Страница 11: ...Ramp Differential Expansion Monitor Operation 8 4 4 1 3 0 1 Blank Page i v...
Страница 13: ...Ramp Differential Expansion Monitor Operation 8 4 4 1 3 0 1 Blank Page v i...
Страница 30: ...3300 46 RAMPDIFFERENTIAL EXPANSION MONITOR MAINTENANCE MANUAL BENTLY r NEVADA PART NO 84414 01...
Страница 33: ...Ramp Differential Expansion Monitor Maintenance 84414 01 Blank Page i v...
Страница 35: ...Ramp Differential Expansion Monitor Maintenance Blank Page 84414 01 v i...
Страница 74: ...Ramp Differential Expansion Monitor Maintenance Appendix SCHEMATICS AND PWA DRAWINGS 84414 01 Appendix...
Страница 80: ...i w W2 19 E 1 Ramp Differential Expansion Monitor Schematic Sheet 6 of 11...
Страница 82: ...f 99 9 L9 9 9 9 j T Ramp Differential Expansion Monitor Schematic Sheet 8 of 11...
Страница 84: ...I 1 I E l i l t L_ C I i J _ 1 _ 1 I Ramp Differential Expansion Monitor Schematic Block Diagram Sheet 10 of 11...