(I2)-Si len cing: If the re la ted FC500MFI in put is ac ti va ted, si len ce a ble out puts
and the buz zer of the con trol pa nel are swit ched off. A new alarm shall re so und
only the buz zer, not the out puts. If si len ced from the
Sim pli fied con trol in ter fa -
ce
, the system shall be un si len ce a ble only from it, not from the con trol pa nel or
from the re pe a ters. If si len ced from any ot her po int, the system shall be un si len -
ce a ble also from the
Sim pli fied con trol in ter fa ce
.
Ø
(I3)- Di sa ble com mu ni ca tor : If the re la ted FC500MFI in put is ac ti va ted, all the
system com mu ni ca tors shall be di sa bled. It shall be pos si ble to ena ble com mu ni -
ca tors aga in only from the
Sim pli fied con trol in ter fa ce
.
Ø
(I4)- Test com mu ni ca tor: If the re la ted FC500MFI in put is ac ti va ted, the com mu -
ni ca tion ac tions pro gram med for con trol pa nel alarm shall be per for med.
Ø
(I5)-
Acti va tion unit
OFF: if the re la ted FC500MFI in put is ac ti va ted, the
Acti va -
tion unit
shall be di sa bled via the de di ca ted MIO or QIO mo du le. It shall not be
pos si ble to di sa ble the
Acti va tion unit
in case of fire alarm. If the
Acti va tion
unit
has been di sa bled from the con trol pa nel or from the re pe a ters, it shall not
be pos si ble to ena ble it from the
Sim pli fied con trol in ter fa ce
and vice ver sa
.
+
The
Acti va tion unit
will en su re that ac ti va tion of fire-fig hting de vi ces will oc cur
only in the event of real dan ger. The con nec ted so le no id val ve will be ac ti va ted
when the Mo
du
le in
puts de
tect alarm sta
tus for the pro
gram
med time
(EXTINGUISHMENT DELAY).
For in put ac ti va tion, vol ta ge free and Nor mally Open (N.O.) con tacts in standby sho -
uld be used.
+
The ac tions con nec ted to I1, I2, I3, I4, and I5 in puts are only pos si ble at le vel 2
(see FC500 con trol pa nel le vels), for this re a son the ac cess to the de vi ce is per -
mit ted only to aut ho ri zed per sons, for exam ple pro tec ting it with a key
+
A switch sho uld be con nec ted with in puts 2, 3 and 5 (which are sen si ti ve to the le -
vel), a pu shbut ton key with the in puts 1 and 4 (which are sen si ti ve to the trig ger).
The switch re ma ins in the po si tion whe re it was pla ced, the pu shbut ton in ste ad,
au to ma ti cally put in the po si tion of rest.
LEDs of the fire bri ga de pa nel may be con nec ted to out put ter mi nals O1, O2, O3,
O4 and O5 in or der to di splay the fol lo wing in for ma tion:
Ø
(O1): Pa nel alarm sta tus in di ca tion
Ø
(O2): Di sa bled com mu ni ca tor
Ø
(O3): Out puts si len ced
Ø
(O4): A tran smis sion of com mu ni ca tor is suc ce ssful
Ø
(O5):
Acti va tion unit
ON. This out put shall be ON if the
Acti va tion uni
t is ac ti ve
(i.e. if in put 1 of the de di ca ted MIO or QIO mo du le has been ac ti va ted).
Ø
(O6):
Acti va tion unit
OFF. This out put shall be ON if the
aA cti va tion unit
has been
di sa bled (i.e. if in put 3 of the de di ca ted MIO or QIO mo du le has been ac ti va ted)
.
+
If the to tal cur rent ab sor bed by the LEDs is lo wer than 200mA, it is pos si ble to take
the po wer supply vol ta ge di rectly from the "24V" ter mi nal of the ter mi nal block [
5
]
+
In the same fire pro tec tion system can be only one
Sim pli fied con trol in ter fa ce
.
n
Remote inputs/outputs
For this ope ra ting mode (see also "Input/out put pro gram ming" in the pre vio us sec -
tion), the FC500MFI mo du le may be in stal led at a ma xi mum di stan ce of 1 km (al -
ways use shiel ded ca ble). Use the I1, I2,and I3 in put ter mi nals to per form the
fol lo wing pro ce du res (see also Fi gu re 2):
Ø
(I1)-Re set
Ø
(I2)-Si len cing
Ø
(I3) Day/Night - (Clo sed con tact = NIGHT)
The in puts ARE ALL SUPERVISED: the ma xi mum con nec tion re si stan ce is 10 Ohm.
For in put ac ti va tion, vol ta ge free and Nor mally Open (N.O.) con tacts sho uld be
used, con nec ting a 3900 Ohm re si stor in se ries to the lat ter and a 10 Kohm re si stor
in pa ral lel to the ter mi nals, as shown in the fol lo wing fi gu re. If the in put (I3) is ac ti va -
ted (in any FC500MFI in the system, max 4), the con trol pa nel shall be in Night
mode. If it is in standby con di tion, the con trol pa nel shall be in Day mode un til the
Night mode is re que sted by any ot her part (FC500MFI, re pe a ter or con trol pa nel
user in ter fa ce) in the system.
+
Note: in case of net wor ked systems, the Day/Night mode of the ma ster con trol
pa nel shall be set as spe ci fied abo ve; that of the sla ve con trol pa nels shall be the
same, if they have the op tion “Net work com mands” set.
+
I3 Input is con nec ted with a switch, the I1 and I2 in puts are con nec ted with a pu -
shbut tons.
+
The ac tions con nec ted to I1, I2, and I3 in puts are only pos si ble at le vel 2 (see
FC500 con trol pa nel le vels): for this re a son the ac cess to the de vi ce is per mit ted
only to aut ho ri zed per sons, for exam ple such as pro tec ting it with a key
LEDs or RELAYS may be con nec ted to the O1, O2, O3, O4, O5 and O6 out put ter mi -
nals, and will be ac ti va ted un der the fol lo wing con di tions:
Ø
(O1): Pa nel alarm sta tus
Ø
(O2): Re set – Acti va tion will last for the en ti re Re set du ra tion
Ø
(O3): Out puts si len ced sta tus
Ø
(O4): Day/Night in di ca tion (Out put ac ti ve = DAY)
Ø
(O5): Ma ins fa ult
Ø
(O6): Bat tery fa ult
+
If the to tal cur rent ab sor bed by the lo ads is lo wer than 200mA, it is pos si ble to
take the po wer supply vol ta ge di rectly from the "24V" ter mi nal of the ter mi nal
block [
5
].
Programming from the Control Panel
To pro gram the FC500MFI mo du le from the con trol panel, pro ce ed as fol lows:
1.
From the main menu, en ter the pro gram ming scre en by pres sing but ton F1;
2.
From the pro gram ming scre en, se lect op tion num ber 5 (Net work);
3.
On the "Net work" pro gram ming scre en, con firm the "PANEL TYPE" (FC500MFI)
pro gram ming by pres sing the ENTER but ton;
4.
Se lect and ac ti va te one or more FC500MFI mo du les (up to 4); se lect a mo du le
using the ar rows
ï
o
ð
(the
^
symbol which ap pe ars un der the name in di ca tes
which mo du le is cur rently se lec ted), ac ti va te a mo du le using the ar row
ñ
or de -
ac ti va te it using the ar row
ò
: the name of the mo du le, if ac ti va ted, will ap pe ar in
CAPITAL let ters (for exam ple, see ON2 mo du le in the fi gu re be low).
Technical features
Power supply
24 ±15% V
_
Max. absorption
250 mA
Standby absorption
30 mA
Operating temperature
0 ÷ +40 °C
Humidity range
93%RH (no condensing)
Dimensions (L*H*D)
85 x 37.2 x 144.5 mm
6
FC500MFI
Re cy cling warn ing
BENTEL SE CU RITY ad vises its cli ents to dis pose of used de vices (con trol
pan
els, de
tec
tors, sirens, elec
tronic ac
ces
so
ries, etc.) with full re
spect
to wards the en vi ron ment. Methods which could be used includethe re-use of
parts or of whole prod ucts and the re cy cling of prod ucts, com po nents and/or
ma te ri als. For fur ther in for ma tion visit:
www.bentelsecurity.com/index.php?o=environmental
Waste Elec tri cal and Elec tronic Equip ment Di rec tive (RAEE – WEEE)
Within the Eu ro
pean Un
ion
,
this la
bel in
di cates that this prod
uct
should NOT be dis posed of along with do mes tic re fuse. It should be placed
in a suit able bin from where it would be pos si ble to per form re cov ery and
re cy cling operations.
For fur ther in for ma tion vi sit:
www.bentelsecurity.com/index.php?o=environmental
INPUT
3900
ohm
10
Kohm
Sistema lev.3: PROGRAMMA
Option to be programmed
Access level
Indicates the presence
of a connection between
the user interface and the motherboard
Control unit status
Modules to be activated:
(up to 4)
on1 ON2 on3 on4
^
FC500MFI Master Panel