890053-02-00
Page
6
of
40
5
Parameter Setup
Follow the steps below to setup H2P drives to operate as a Lead/Lag system. The H2 Pump Software (H2P) has a
macro group of parameters (MC2 Group) that includes settings for multiple drive / multiple motor control. The MC2
Group includes parameters from other groups, including AP1 Group, PID Group and others. The MC2 Group
parameter list and settings are shown in the table in
Section 6, Macro 2 Group (MC2)
Step 1
:
Upon Power Up, at Run QuickStart, select “Yes”.
Step 2
: At 43 Macro Select, select (2) Lead Lag Sel.
Step 3
: Set the remaining parameters within the Quick Start menu.
Step 4
: Set a unique communication address at parameter COM-01 (Drive ID) in each drive.
•
VFD#1 - COM-
01 to “1”
•
VFD#2 - COM-
01 to “2”
Step 5
: Cycle power after setting the above parameters.
Note:
The default for COM-01 (Drive ID) is “0”. If COM-01 is not set in each drive, the drive will flash a warning
“Int485 St ID” as a reminder to set COM-01 when changing other parameters.
The firmware places the Lead/Lag parameters in a Macro group (MC2). To access the Macro group:
Step 6
: At the first drive with COM-01 set as Drive ID 1, press the MODE button while viewing the upper left
corner of the LCD. Stop when U&M MC2 (User & Macro) is displayed. Set parameters in the MC2 Group. The
Macro group (MC2) includes parameters for Lead/Lag setup and are listed in the table in
•
Data Share: When setting parameters in Drive #1, p
arameter’s designated as “Yes” in the Data
Share column of the parameter table will be changed in all Lag drives in the system.
Note that the
Lead (+) drive must be in the Ready Mode (AUTO LED blinking) to Data Share
. See
Section
. Alternatively, if it is necessary to set or change a specific data shared parameter in
a Lag drive, change it within the Lag drive.