Learning Basic Features
Set the Frequency Reference using the V1 Terminal
You can modify the frequency reference using the V1 input terminal at the control board. Use
voltage inputs ranging from 0 to 10 V (unipolar) or from -10 to +10 V (bipolar) for both directions,
where negative voltage inputs are used for reverse operations. Scaling of the voltage range is done
with In.08 through In.11 (unipolar) and In.12 through In.15 (bipolar). View the input voltage at In.05.
4.1.3.1
Setting a Frequency Reference for 0
–
10 V Input
Set parameter Frq in the Operations group to 2 (V1) and set parameter In.06 (V1 Polarity) to 0
(unipolar). Connect an external 0-10V source (PLC or other) to the V1-CM terminals. When
connecting a potentiometer, use the VR terminal (voltage reference, +10V) as the 10V source. See
connection diagrams below.
[Connecting to external 0-10V source]
[Connecting potentiometer]
0
–
10 V Input Voltage Settings
Group
Cod
e
Name
Setting
Setting Range
Unit
Operation Frq
Frequency reference
source
2 V1
0
–
8
-
In
01
Frequency for maximum
analog input
Maximum
frequency
Start Frequency
–
Max. Frequency
Hz
05 V1 input voltage display
0.00
0.00
–
12.00
V
06 V1 input polarity selection 0 Unipolar
0
–
1
-
07
V1 input filter time
constant
100
0
–
10000
msec
08
V1 minimum input
voltage
0.00
0.00
–
10.00
V
09
Output (%) at V1
minimum
0.00
0.00
–
100.00
%
10
V1 maximum input
voltage
10.00
0.00
–
12.00
V
11
Output (%) at V1
maximum
100.00
0
–
100
%
16 Rotation direction options 0 No
0
–
1
-
17 V1 quantization level
0.04
0.00*, 0.04
–
10.00
%
* Quantizing is disabled if "0" is selected.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...