Perform Basic Operations
890054-00-00
Trip Condition Monitor
The following demonstrates how to monitor fault conditions in the Operation group using the
keypad.
Step
Instruction
Keypad Display
1
Refer to the example keypad display.
An over current trip fault has occurred.
2
Press the [ENT] key, and then the [▲] key.
The operating frequency at the time of the fault (30.00
Hz) is displayed.
3
Press the [▲] key.
The output current at the time of the fault (5.0 A) is
displayed.
4
Press the [▲] key.
The operation status at the time of the fault is displayed.
ACC on the display indicates that the fault occurred
during acceleration.
5
Press the [STOP/RESET] key.
The inverter resets and the fault condition is cleared. The
frequency reference is displayed on the keypad. The fault
is stored in the Fault History, Parameters Pr.91 ~ Pr.95.
Note
You can review the fault history with parameters Pr.91 through Pr.95 in the Protection
Group.