SAFETY
Emergency stop connection. WARNING: Mains power supply.
Remove the jumper and connect a N.C., changeover switch, suited for the mains voltage.
See wire diagram.
Note: The emergency stop cuts power supply to the motor and supplies the positive electric
brake.
36-37-38
Selection of
Mains power
supply
Selection of power supply voltage, short-circuit:
36 and 37 for three-phase power supply (400Vac)
37 and 38 for single-phase power supply (230Vac)
39-40
Single-phase
power supply
Input, single-phase mains power supply 230Vac/50Hz (39-L / 40-N)
39-40-41
Three-phase
power supply
Input, or three-phase mains power supply, 400Vac/50Hz (39-R / 40-S / 41-T).
Programming
The various functions of the control unit can be programmed by using the LCD display provided on the side of the unit and by set-
ting the desired values on the Programming Menu, as described hereunder.
The Parameters Menu allows for the presetting of a digit value to a function, like an adjustment trimmer.
The Logic Menu allows for the activation and deactivation of a function, like the setting of a Dip-Switch.
The special functions follow the Parameters Menu and the Logic Menu and can vary according to the type of control unit or soft-
ware review.
To access programming :
1 – Press the <PG> push-button, the rst Parameters Menu “PAR” appears on the display.
2 – Select the desired menu by using the <+> or <-> keys (PAR>>LOG>>NMAN>>RES>>PAR>>....).
3 – Press the <PG> push-button, the display shows the rst function available in the Menu.
4 – By using the <+> or <-> keys select the function to be modied.
5 – Press the <PG> push-button, the currently preset value for the selected function is displayed.
6 – By using the <+> or <-> keys, select the value which is to be assigned to the function.
7 – Press the <PG> push-button and the “PRG” message is displayed. This means that programming has been completed.
Note:
When upon a Function Menu, press keys <+> e <-> simultaneously to pass to higher menu without making any change.
If <+> and <-> keys are pressed simultaneously when the display is off, the software version of the board is shown.
Keep either keys <+> or <-> pressed to speed up the increase/decrease of values.
After 60 sec wait, the control unit exits the Programming mode and the display switches off.
Parameters, Logic and Special Functions
In the tables hereunder the single functions available in the control unit are shown.
MENU
FUNCTION
Settable values
MIN-MAX-(Default)
MEMO
P
ARAMETERS
TCA
Automatic closure time. Active with logic “TCA”= ON only.
At the end of the preset time, the control unit sends a closure control
signal.
1-240-(40s)
TM
Motor operating time. The operation time is adjusted during the opening
and closing phases of the motor.
5-180-(40s)
Tped
The stroke time of the gate leaf is adjusted during the partial opening
phase (pedestrian mode).
5-180-(10s)
SnSo
* The amperometric sensor sensitivity is adjusted in the opening phase.
This is operating only with logic AMP:ON.
1:maximum sensitivity - 99:minimum sensitivity.
The sensor triggering in the opening phase stops the movement immedi-
ately.
1-99-(20%)
SnSC
* The amperometric sensor sensitivity is adjusted in the closing phase.
This is operating only with logic AMP:ON.
1: maximum sensitivity - 99:minimum sensitivity.
When the sensors triggers in the closing phase, the gate stops immedi-
ately and a reversion movement (opening) starts for approximately 3 sec.
1-99-(20%)
TLS
The activation time of the courtesy light is adjusted. The contact closes
with the beginning of the opening operation. The time counting starts only
with gate completely closed.
1-240-(1s)
SaFM
This is operating only with logic SMOT:ON. The motor protection switch
triggering is adjusted. The value is expressed in Amperes.
1:
triggering of protection switch at 1 Ampere of consumption
14: protection disabled.
1-14-(6A)
* WARNING:
An incorrect setting of these parameters may cause danger. Please comply with regulations in force!