11
CONTROL UNIT CP.B24-SW
ELECTRICAL CONNECTIONS
The following table shows the electrical connections in Fig. 1:
Terminals
Function
Description
SEL 115/230
Mains power supply selection
230 Vac 50/60 Hz (from 207 to 253 Vac) jumper M7 OPEN
115 Vac 50/60 Hz (from 102 to 125 Vac) jumper M7 CLOSED
L/N/GND
Power supply
Mains power supply input 115Vac/230Vac selectable via M7 jumper
MOT
Motor
Quick connector for the connection of 24 Vdc motor
COM/SWO/SWC
Adjustable
Quick connector for the connection of the limit switches
COM: Common - SWO Limit Switch Opens (N.C. contact) - SWC Limit switch closes
(N.C. contact)
ANT/SHIELD
Antenna
Built-in radio receiver antenna connection
ANT: Signal / SHIELD: Display
COM
General
Common for all control inputs.
S.S.
Step-by-Step
Step-by-step key input (N.O. contact).
The control unit executes a command at each S.S. impulse according to the se-
quence:
OPENS>STOP>CLOSES>STOP>OPENS or OPENS>CLOSES>OPENS.
See dip switch 2
STOP
STOP
STOP key input (N.C. contact)
Settable as a PED key (N.O. contact) see dip switch 2
PHOT
Photocell
Photocell input (N.C. contact) active in the closure and opening phase according to
the setting of dip switch 2
BLINK
Flashing
24Vdc flashing connection 15W max.
+ 24V -
24 Vac/dc
Power supply output accessories 24Vdc/500mA max.
AUX
Auxiliaries output
Clean contact (N.O.) configurable using Dip Switch 1 as SCA (gate open indicator
light) or second radio channel.
J6
X.BE
Quick connector for KNX interface card (item X.BE - See paragraph KNX)
M6
Battery charger
Quick connector for optional battery charger card connection.
ARC TRANSMITTERS
IMPORTANT, PLEASE READ CAREFULLY:
The radio receiver in this product is compatible only with ARC (Advanced Rolling Code) transmitters which, thanks to 128 bit coding,
guarantee superior anti-copying security.
AUTOSET
CAUTION! THE AUTOSET PROCEDURE DESCRIBED BELOW IS MANDATORY!
During the AUTOSET phase, the control unit performs a number of opening and closing movements during which essential operating parameters are
set, including:
- Start- and end-of-run positions.
- Start of the slowing phases.
- Torque values applied during panel movement.
- Recognition of the device connected to the PHOT input.
Procedure:
1) Position the leaf in th e CLOSURE position (check activation of the SWC limit switch)
2) With the control unit connected to the mains, press and hold down the PU1 + PU2 keys until the 3 red LEDs light up cyclically.
3) The AUTOSET procedure starts, some opening and closing movements are commanded.
4) At the end of the procedure the panel stops in the open position and the LED lights remain steady for 5s to confirm AUTOSET
correctly carried out.