System description
20
RCMS460-490_D00067_03_M_XXEN/12.2017
RCMS…-D4/RCMS…-L4
The function of device version RCMS…-D4/RCMS…-L4 corresponds to the
function described before. The functions of measuring channels k9 … k12
vary from those described before. They are exclusively designed for current
measurements with type A measuring current transformers (measuring ran-
ge 100 mA … 125 A). For that reason, the measuring channels k9…k12 cannot
be used in combination with W…AB series measuring current transformers or
as digital inputs.
Choice of RCMS and measuring channels