Bender RCMB102 Скачать руководство пользователя страница 16

Function

16

TGH1475en/11.2012

2.8 Measuring range and switching times

Measuring range

The measuring range of the residual current is 0…30 mA according to IEC60755.

Switching time residual current monitoring module (without switching device)

The maximum switching times of the output X12 is dependent on the residual current.

 
 

2.9 Fault detection and the resulting technical reactions

Residual current

I

Δ

n

I

Δ

n

5

 I

Δ

n

Switching time T1 of the output X12

180 ms

100 ms

20 ms

Note

:

In order to comply with the switching times required by the standard (IEC 60755),
the 

switching time of the circuit-breaker 

(incl. driver circuit) 

must not exceed

 

20 ms!

Type of fault

Detection

Response

Wire break in the
residual current transformer

Frequency measurement of the 
measuring oscillator

X1 = 5.0 V
X12 =  HIGH 

Short-circuit in the residual cur-
rent transformer winding

Frequency measurement of the 
measuring oscillator

X1 = 5.0 V
X12 =  HIGH 

Constant output voltage at the 
measuring oscillator

Frequency measurement of the 
measuring oscillator

X1 = 5.0 V
X12 =  HIGH  

Failure main oscillator

Reset by internal watchdog

X1 = 5.0 V or X1 = 0 V
X12 =  HIGH  

Supply voltage failure

Monitoring module connects and discon-
nects residual current monitoring

X1 = 5.0 V or X1 = 0 V
X12 =  HIGH  

Open collector output
constantly at LOW level

Self test to check whether output X12 
switches to HIGH for 4.6 s when supply 
voltage is connected; for details about 
time T4 refer to page 12

Charging control electronics 
detects fault after connecting to 
the supply voltage 

Analogue output X1 constantly 
at LOW level

Output voltage outside the permissible 
voltage range

Disconnection by charging con-
trol electronics

Storage cell of the computer 
system defective

Detection by memory self test

X1 = 5.0 V
X12 =  HIGH 

Loss of return addresses from 
subprograms

Response of internal watchdog

X1 = 5.0 V
X12 =  HIGH  

Содержание RCMB102

Страница 1: ...Operating Manual RCMB102 AC DC sensitive residual current monitoring module for installation into electric vehicle charging stations Software version D395 V1 TGH1475en 11 2012...

Страница 2: ...ing only with permission of the publisher Subject to change Bender GmbH Co KG Londorfer Str 65 35305 Gr nberg Germany Postfach 1161 35301 Gr nberg Germany Tel 49 6401 807 0 Fax 49 6401 807 259 E mail...

Страница 3: ...ction 7 2 3 Starting sequence 8 2 4 Analogue voltage output X1 10 2 5 Switching output X12 10 2 6 Control input X10 10 2 6 1 Cyclical self test 10 2 6 2 Reset function 11 2 6 3 Impulse duration for ac...

Страница 4: ...7 3 3 Example applications 18 3 3 1 The circuit breaker is controlled by the charging control electronics and the switching output X12 18 3 3 2 The circuit breaker is controlled by the charging contro...

Страница 5: ...identify important instructions and information The meaning of these symbols is explained below 1 3 Intended use The AC DC sensitive residual current monitoring module RCMB102 is used for monitoring...

Страница 6: ...t accept any liability for injury to persons or damage to property resulting from errors or mistakes in this manual 1 5 Personnel Only appropriately qualified personnel may work on the Bender product...

Страница 7: ...he residual current monitoring module detects the residual current caused by leakage and residual currents in the conductors passed through the measuring current transformer The residual current monit...

Страница 8: ...e enables the switching output X12 LOW level Test current supply 5 The test winding is supplied with test current for 2 s two stage test current The resulting measured value is available at X1 and the...

Страница 9: ...X12 HIGH Delay 0 05 0 1 ms X12 HIGH 10 11 ms X10 50 s HIGH No Yes No Yes Yes Yes No No X10 100 s HIGH Yes No No Yes Switch on test current through test winding Test current measurement Switch off tes...

Страница 10: ...toring module the switching output X12 will be disabled and signalled by the open collector output X12 Fig 2 2 Open collector Only when the measured value of the residual current falls below 10 mA for...

Страница 11: ...6 3 Impulse duration for activating a reset When a LOW level is applied at the control input X10 of the residual current monitoring module for T 530 ms no reset will be carried out The outputs X1 and...

Страница 12: ...ibration T2 50 100 s X12 X1 T4 4 6 s T3 10 11 ms Begin of calibration process End of calibration process Start of residual current measurement HIGH LOW LOW HIGH t2 T5 0 1 s T6 0 15 s T7 0 85 s T9 5 ms...

Страница 13: ...0 100 s is applied at the control input X10 Calibration starts within 10 11 ms T3 The RCMB disables the open collector switching output X12 HIGH and carries out an offset measurement The DC component...

Страница 14: ...abled after 2 3 s If X10 is maintained at LOW level at the end of the self test X12 remains disabled until X10 has reached HIGH level for at least 5 ms Refer to the diagram in chapter 2 6 4 for more i...

Страница 15: ...current see chapter 2 8 If the residual current monitoring module detects values outside the measuring range the analogue output X1 will be set to 4 85 V As soon as the residual current drops to 10 mA...

Страница 16: ...nt transformer winding Frequency measurement of the measuring oscillator X1 5 0 V X12 HIGH Constant output voltage at the measuring oscillator Frequency measurement of the measuring oscillator X1 5 0...

Страница 17: ...ing current transformer Plug designation Description X1 Analogue voltage output X2 US Voltage supply 12 V via current limiting or 100 mA fuse recommended X3 GND ground X4 not connected X9 GND ground X...

Страница 18: ...ctronics The circuit breaker is controlled by the charging control electronics software The switching output X12 and the analogue output X1 are monitored by the charging system to ensure that the outp...

Страница 19: ...V 10 mA Tolerance at 1 5 10 mA 0 20 1 mA Tolerance at 10 50 mA 0 20 Tolerance at 0 15 V 50 mV 0 mV Tolerance at 4 85 V 150 mV 50 mV Output resistance at the measurement outputX1 1 k short circuit proo...

Страница 20: ...lassification of climatic conditions Ambient temperature during operation 25 C 80 C Ambient temperature during transport 40 C 80 C Ambient temperature during long time storage 25 C 80 C Relative humid...

Страница 21: ...Technical data 21 TGH1475en 11 2012 4 3 Dimension diagrams Dimensions are given in mm...

Страница 22: ...Technical data 22 TGH1475en 11 2012...

Страница 23: ......

Страница 24: ...Bender GmbH Co KG Londorfer Str 65 35305 Gr nberg Germany Postfach 1161 35301 Gr nberg Germany Tel 49 6401 807 0 Fax 49 6401 807 259 E Mail info bender de com Web http www bender de com...

Отзывы: