27
RCMA426H-DCB_D00066_00_M_XXEN/05.2014
6. Technical data
6.1
Data RCMA426H-DCB-2 in table form
( )* = factory setting
Insulation coordination acc. to IEC 60664-1 / IEC 60664-3
Rated insulation voltage ....................................................................................................................................... 250 V
Overvoltage category/ pollution degree.................................................................................................................. III/3
Rated impulse voltage...............................................................................................................................................4 kV
Protective separation (reinforced insulation) between.......................................... (A1, A2) - (k/l, T/R) - (21, 22, 24)
Voltage tests according to IEC 61010-1.............................................................................................................. 2.21 kV
Supply voltage
Supply voltage range
U
s
................................................................................................................. AC/DC 100…250 V
U
s
...................................................................................................................................................... AC/DC 70…300 V
Frequency range
U
s
................................................................................................................................... 42…460 Hz
Power consumption ......................................................................................................................................... ≤ 6.5 VA
Measuring circuit
Internal measuring current transformer, diameter ............................................................................................ 13 mm
Rated voltage (measuring current transformer) .................................................................................................. 2.5 kV
Rated frequency ........................................................................................................................................... 0…150 Hz
AC/DC measuring range .............................................................................................................................. 0…40 mA
Relative uncertainty 0…20 Hz ....................................................................................................... -33 %…+100 %
Relative uncertainty 20…90 Hz ................................................................................................................. 0…-33 %
Relative uncertainty 90…150 Hz .................................................................................................................. ±17.5 %
Response value
Rated residual operating current
I
Δ
n
.................................................................................................................... 6 mA
Time behaviour
Start-up delay
t
.................................................................................................................... operating time
t
ae
+ 3.2 s
Operating time
t
ae
acc. to UL943 ........................................................................................... see diagram on page 32
Содержание RCMA426H-DCB
Страница 6: ...Making effective use of this document 6 RCMA426H DCB_D00066_00_M_XXEN 05 2014...
Страница 8: ...Safety instructions 8 RCMA426H DCB_D00066_00_M_XXEN 05 2014...
Страница 16: ...Installation and connection 16 RCMA426H DCB_D00066_00_M_XXEN 05 2014...
Страница 37: ...37 RCMA426H DCB_D00066_00_M_XXEN 05 2014...
Страница 38: ...38 RCMA426H DCB_D00066_00_M_XXEN 05 2014...
Страница 39: ......