![Bender RCMA423AS Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/bender/rcma423as/rcma423as_manual_2731740039.webp)
39
RCMA423AS_D00157_01_M_XXEN/08.2016
6. Technical data
6.1
Data in tabular form
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
RCMA423AS-D-1:
Rated insulation voltage ................................................................................................................ 100 V
Overvoltage category/ pollution degree............................................................................................ III/3
Rated impulse voltage.................................................................................................................... 2.5 kV
RCMA423AS-D-2:
Rated insulation voltage ................................................................................................................ 250 V
Overvoltage category/ pollution degree............................................................................................ III/3
Rated impulse voltage....................................................................................................................... 4 kV
Supply voltage
RCMA423AS-D-1:
Supply voltage range
U
s
(acc. AS/NZS 2081:2011) ........................... AC 32…60 V / DC 19,2…78 V
Operating range
U
s
.............................................................................. AC 16…72 V / /DC 9.6…94 V
Frequency range
U
s
......................................................................................................DC, 42…460 Hz
RCMA423AS-D-2:
Supply voltage range
U
s
(acc. AS/NZS 2081:2011) ............................................... AC/DC 140…250 V
Operating range
U
s
................................................................................................... AC/DC 70…300 V
Frequency range
U
s
......................................................................................................DC, 42…460 Hz
Protective separation (reinforced insulation) between................... (A1, A2) - (k/l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test according to IEC 61010-1 .................................................................................................... 2.5 kV/1 Min.
Power consumption ......................................................................................................................................... ≤ 6,5 VA