Function
18
RCMA420-DM_D00060_02_M_XXEN/06.2016
3.2.10 Erasable history memory
The first alarm value that occurs will be saved in this memory. The memory can
be cleared via the menu HiS.
3.2.11 External, combined test/reset button T/R
Reset = Pressing the external button < 1.5 s
Test
= Pressing the external button > 1.5 s
3.2.12 Fault memory
The fault memory can be activated, deactivated or set to continuous mode
(con). If the fault memory is set to "con" mode, the alarm parameters remain
stored even on failure of the supply voltage. Stored alarms can be reset by me-
ans of the reset button R.
3.2.13 Interface option
The device provides an analogue interface with galvanic isolation. One of
three output signals can be selected from the associated menu.To receive no
error (full scale of the connected measuring device), only use the output you
have selected via the software:
– DC 0…400 μA
Current output for Bender measuring instruments of the 96.. series.
– DC 0…20 mA / DC 4…20 mA
Standardized current output with selectable current ranges.
– DC 0…10 V
Standardized voltage signal.