Voltage measurement
18
PEM735-measuring_case_D00240_00_M_XXEN/12.2015
5. Voltage measurement
5.1 Overview material for voltage measurement
Fig. 5.1: Overview material for voltage measurement
From left to right: secured measuring voltage cables, crocodile clips, safety crocodile clips,
magnetic test probes
Connect the measuring voltage cable to the corresponding socket L1…3/N/PE at the
side of the case.
To connect the secured side of the measuring voltage cable you have the following op-
tions:
Crocodile clips (PE always, for other cables optional)
Safety crocodile clips for use with push-wire terminals
Magnetic test probes to enable the screws to make contact with the circuit
breaker
Risk of fatal injury from electric shock!
First
connect
the laboratory plugs to the case
.
Only after this step the measuring voltage cables may be connected to the
system.
Risk of fatal injury from electric shock!
Incorrect wiring of the measuring voltage cables may cause a short-circuit
of the installation, arcs and high short-circuit currents.
Never use measuring cables without integrated fuse
for voltage
coupling!
The
side of the measuring voltage cable
with the fuse
(longer plug)
must be connected to the installation
.
DANGER