Power Quality and Energy Measurement 
PEM330/PEM333

Product description
The universal measuring device PEM330/333 is used to record and indicate electrical 
quantities of a public electricity network. The scope of measurements ranges from currents 
and voltages through energy consumption and performance to total harmonic distortion 
and voltage quality assessment. The active energy measurements are in compliance with 
the DIN EN 62053-22 class 0.5 S accuracy standard.The current inputs are connected via 
external …/1 A or …/5 A measuring current transformers.

Typical application
•   As a compact device for front panel mounting, the PEM330/333 is a replacement  

for analogue indicating instruments

•   Typical application in low and medium-voltage networks  

(via measuring voltage transformer)

•  Power quality monitoring
•   Collection of relevant data for energy management systems
•   Energy consumption allocation to cost accounting centers

Description of function
•  Sampling rate of the measuring channels: 1,6 kHz
•   Calculation of the total  harmonic distortion THD

U

/THD

I

: up to the 15th harmonics

•  Password protection
•  Easy installation with mounting clips, no tools required 
•  Inputs and outputs (PEM333 only):
  – 2 digital outputs
  –  6 user-programmable setpoints (response values, response delay 0…9999 seconds)
  –  System protocol: 32 events, setup changes, DI/setpoint status changes, DO operations
•  Communication (PEM333 only):
  – Electrically isolated RS-485 interface (1,200 bit/s to 19,200 bit/s)
  – Modbus-RTU protocol

Standards
The universal measuring device for Power Quality and Energy Measurement PEM330/PEM333 
was developed in accordance with the following standards: DIN EN 62053-22 (VDE 0418 
Part 3-22), DIN EN 61557-12 (VDE 0413-12)

Device features
•   Accuracy class according to IEC 62053-22: 

0.5 S

•  Measured quantities
  –   Phase  voltages 

U

L1

U

L2

U

L3

 in V

  –   Line  voltages 

U

L1L2

U

L2L3

U

L3L1

 in V

  –   Phase  currents 

I

1

I

2

I

3

 in A

  –  Neutral current (calculated) 

I

4

 in A

  –   Frequency 

f

 in Hz

  –  Phase angle for 

U

 and 

I

 in °

  –  Power per phase conductor S in kVA, P 

in kW, Q in kvar

  –  Total power S in kVA, P in kW, Q in kvar
  –  Displacement factor cos (φ)
  –  Power factor λ
  –  Active and reactive energy import in 

kWh, kvarh

  –  Active and reactive energy export in 

kWh, kvarh

  –  Voltage unbalance in %
  –  Current unbalance in %
  –  Harmonic distortion (THD) for 

U

 and 

I

  – k-factor for 

I

•   Programmable setpoint monitoring 

(PEM333 only)

•   LED pulse outputs  for active and  

reactive energy

•   Modbus/RTU communication via RS-485 

(PEM333 only)

•  2 digital outputs (PEM333 only)
•   Demands of energy and current for  

particular time frames

•  Peak demands with timestamps

0.5S

PEM330

PEM333

RS-485

Digital inputs

2

Digital outputs

2

Sampling rate

1.6 kHz

1.6 kHz

THD calculation

15.

15.

Features

Содержание PEM330

Страница 1: ...Power Quality and Energy Measurement PEM330 PEM333 PEM330 333_D00004_00_D_XXEN 06 2013 ...

Страница 2: ...er programmable setpoints response values response delay 0 9999 seconds System protocol 32 events setup changes DI setpoint status changes DO operations Communication PEM333 only Electrically isolated RS 485 interface 1 200 bit s to 19 200 bit s Modbus RTU protocol Standards The universal measuring device for Power Quality and Energy Measurement PEM330 PEM333 was developed in accordance with the f...

Страница 3: ...ton OK in the menu Press the SETUP button 1 5 s to enter leave the Setup menu kvarh kWh PEM333 LINETRAXX SYSTEM PHASE ENERGY SETUP OK 1 2 3 4 5 6 7 Example for system set up Modbus TCP Ethernet BMS 1 12 Modbus RTU Fileserver L PEN PE L N PE U I Modbus TCP Modbus RTU PAS PEM7xx U I NSHV UV1 1 12 RCMS UV2 U I U I U I RCMS Modbus TCP Modbus RTU Modbus TCP PEM5xx PEM5xx Modbus RTU PEM3xx PEM7xx CP700 ...

Страница 4: ...e to be protected by a fuse 3 Digital inputs 4 Digital outputs N O contacts Three phase 4 wire system TN TT IT systems The PEM can be used in three phase 4 wire systems independent of the type of distribution system TN TT IT system Three phase 3 wire system The PEM can be used in three phase 3 wire systems The line to line voltage must not exceed AC 400 V Connection via voltage transformers The co...

Страница 5: ...ue 0 05 of full scale value Neutral current I4 1 of full scale value Frequency 0 02 Hz Phase position 1 Activeenergymeasurementaccordingto DINEN62053 22 VDE0418Part3 22 r m s voltagemeasurementaccordingto DINEN61557 12 VDE0413 12 chapter4 7 6 r m s phasecurrentmeasurementaccordingto DIN61557 12 VDE0413 12 chapter4 7 5 Frequencymeasurementaccordingto DINEN61557 12 VDE0413 12 chapter4 7 4 Interface ...

Страница 6: ...ER Group Subject to change PEM330 333_D00004_00_D_XXEN 06 2013 Schw Bender GmbH Co KG Germany Dimension diagram Dimensions in mm 96 80 62 96 91 18 18 62 96 91 Panel cut out Dimensions in mm 92 92 Interface Digital inputs outputs Current input Type Art No 5 A PEM330 B 9310 0330 1 A PEM330 251 B 9310 0331 RS 485 2 2 5 A PEM333 B 9310 0333 1 A PEM333 251 B 9310 0334 Ordering information ...

Отзывы: