Power Quality and Energy Measurement
PEM330/PEM333
PEM330-333_D00004_00_D_XXEN/06.2013
Страница 1: ...Power Quality and Energy Measurement PEM330 PEM333 PEM330 333_D00004_00_D_XXEN 06 2013 ...
Страница 2: ...er programmable setpoints response values response delay 0 9999 seconds System protocol 32 events setup changes DI setpoint status changes DO operations Communication PEM333 only Electrically isolated RS 485 interface 1 200 bit s to 19 200 bit s Modbus RTU protocol Standards The universal measuring device for Power Quality and Energy Measurement PEM330 PEM333 was developed in accordance with the f...
Страница 3: ...ton OK in the menu Press the SETUP button 1 5 s to enter leave the Setup menu kvarh kWh PEM333 LINETRAXX SYSTEM PHASE ENERGY SETUP OK 1 2 3 4 5 6 7 Example for system set up Modbus TCP Ethernet BMS 1 12 Modbus RTU Fileserver L PEN PE L N PE U I Modbus TCP Modbus RTU PAS PEM7xx U I NSHV UV1 1 12 RCMS UV2 U I U I U I RCMS Modbus TCP Modbus RTU Modbus TCP PEM5xx PEM5xx Modbus RTU PEM3xx PEM7xx CP700 ...
Страница 4: ...e to be protected by a fuse 3 Digital inputs 4 Digital outputs N O contacts Three phase 4 wire system TN TT IT systems The PEM can be used in three phase 4 wire systems independent of the type of distribution system TN TT IT system Three phase 3 wire system The PEM can be used in three phase 3 wire systems The line to line voltage must not exceed AC 400 V Connection via voltage transformers The co...
Страница 5: ...ue 0 05 of full scale value Neutral current I4 1 of full scale value Frequency 0 02 Hz Phase position 1 Activeenergymeasurementaccordingto DINEN62053 22 VDE0418Part3 22 r m s voltagemeasurementaccordingto DINEN61557 12 VDE0413 12 chapter4 7 6 r m s phasecurrentmeasurementaccordingto DIN61557 12 VDE0413 12 chapter4 7 5 Frequencymeasurementaccordingto DINEN61557 12 VDE0413 12 chapter4 7 4 Interface ...
Страница 6: ...ER Group Subject to change PEM330 333_D00004_00_D_XXEN 06 2013 Schw Bender GmbH Co KG Germany Dimension diagram Dimensions in mm 96 80 62 96 91 18 18 62 96 91 Panel cut out Dimensions in mm 92 92 Interface Digital inputs outputs Current input Type Art No 5 A PEM330 B 9310 0330 1 A PEM330 251 B 9310 0331 RS 485 2 2 5 A PEM333 B 9310 0333 1 A PEM333 251 B 9310 0334 Ordering information ...