69
NGRM700_D00292_04_M_XXEN/09.2019
13. Technical data
13.1
Tabular data
Insulation coordination according to IEC 60664-1/IEC 60664-3/DIN EN 50178
Definitions
Measuring circuit 1 (IC1) ............................................................................................................................................(L1, L2, L3)
Supply circuit (IC2) ......................................................................................................................................................... (A1, A2)
Measuring circuit/Control circuit (IC3)............................................................................................... (RS, E, CT), (X1, Ethernet)
Output circuit 1 (IC4) .................................................................................................................................................(11, 12, 14)
Output circuit 2 (IC5) .................................................................................................................................................(21, 22, 24)
Output circuit 3 (IC6) .................................................................................................................................................(31, 32, 34)
Rated voltage .......................................................................................................................................................................690 V
Overvoltage category................................................................................................................................................................. III
Rated impulse voltage
IC1 / (IC2…6)....................................................................................................................................................................... 8 kV
IC2 / (IC3…6)....................................................................................................................................................................... 4 kV
IC3 / (IC4…6)....................................................................................................................................................................... 4 kV
IC4 / (IC5…6)....................................................................................................................................................................... 4 kV
IC5 / (IC6)............................................................................................................................................................................... 4 kV
Rated insulation voltage
IC1 / (IC2…6).....................................................................................................................................................................800 V
IC2 / (IC3…6).....................................................................................................................................................................250 V
IC3 / (IC4…6).....................................................................................................................................................................250 V
IC4 / (IC5…6).....................................................................................................................................................................250 V
IC5 / (IC6).............................................................................................................................................................................250 V
Pollution degree exterior ........................................................................................................................................................... 3
Safe isolation (reinforced insulation) between
IC1 / (IC2…6)............................................................................................................................ overvoltage category III, 800 V
IC2 / (IC3…6)............................................................................................................................ overvoltage category III, 300 V
IC3 / (IC4…6)............................................................................................................................ overvoltage category III, 300 V
IC4 / (IC5…6)............................................................................................................................ overvoltage category III, 300 V
IC5 / (IC6).................................................................................................................................... overvoltage category III, 300 V
Содержание NGRM700
Страница 1: ...NGRM700 Neutral Grounding Resistor Monitor NGRM700_D00292_04_M_XXEN 09 2019 Manual EN ...
Страница 32: ...Connection 32 NGRM700_D00292_04_M_XXEN 09 2019 ...
Страница 38: ...User interface FP200 NGRM 38 NGRM700_D00292_04_M_XXEN 09 2019 ...
Страница 60: ...Initial commissioning 60 NGRM700_D00292_04_M_XXEN 09 2019 ...
Страница 64: ...Test cycle 64 NGRM700_D00292_04_M_XXEN 09 2019 ...
Страница 68: ...Error codes 68 NGRM700_D00292_04_M_XXEN 09 2019 ...
Страница 79: ......