 7

 

I

C

aution

Risk of injury due to accessible live conductors! 

The measuring current transformer must be connected to the corresponding evaluator before 

the first use and before commissioning of the monitored system.

 

i

Do not route any shielded cables through the measuring current transformer.

 

i

Application in railway vehicles / DIN EN 45545-2:2016!  

If the horizontal or vertical distance to adjacent components which do not meet the require-

ments in table 2 of DIN EN 45545-2 is less than 20 mm or less than 200 mm respectively, they 

are to be regarded as grouped. Refer to DIN EN 5545-2 chapter 4.3 Grouping rules.

Completing and checking installation

The installation must be completed with a functional test: Press the "T" button for 5…10 s.
The system operator is obliged to have the MRCD protective devices checked at regular intervals 

by an electrically skilled person to ensure that they are functioning properly. This requirement is 

deemed to be satisfied for normal and environmental conditions if the test intervals mentioned in 

DGUV V3 (German Social Accident Insurance Regulation 3) are adhered to. The test intervals are 

to be interpreted in accordance with the risk assessment.
The recurrent tests must include at least the following:
•  Testing the environmental conditions for pollution, mechanical damage or insulation damage.
•  To trip the circuit breaker, the integrated or the external test button is to be pressed.

All current-carrying cables must be routed through the mea-

suring current transformer.

PE

L1

L2

L3

N

P1 (K): YE

P2 (L): GY

Never route an existing protective conductor through the  

measuring current transformer.

The primary conductors should only be bent from the specified 

minimum distance. The minimum bending radius specified by 

the manufacturers for the conductors used must be observed.

*   Distance to 90° angle = 2 x outer diameter.

*

*

The cables must be aligned with the centre of the measuring  

current transformer.

Содержание MRCDB300 Series

Страница 1: ...Quickstart guide EN MRCDB300 series_D00343_05_Q_XXEN 01 2022 MRCDB300 series AC DC sensitive residual current monitoring module for MRCD applications...

Страница 2: ...e in earthed power supplies TN and TT systems up to 800 V is possible These devices are suitable for monitoring AC and DC fault currents type B Any other use than that described in this document is re...

Страница 3: ...ts must be plugged together and calibrated during commissioning Device view 21 22 24 11 12 14 K1 K2 3 4 7 8 9 1 2 5 6 10 11 12 11 12 13 14 No Terminal Meaning 1 24V Supply voltage US 2 GND 3 D1 Contac...

Страница 4: ...ce i The use of a type 2 surge protection de vice SPD is mandatory due to possible impulse voltages and in order to comply with normative requirements The surge protection device must be con nected up...

Страница 5: ...s the set limit of the prewarning de energised energised Alarm state off lights The device is supplied with the specified voltage and monitors the primary circuit A fault current flows which exceeds t...

Страница 6: ...ys switch to safe state during offset calibration system is switched off Procedure of the first offset calibration Action LED 1 Install the measuring current transformer in the system off 2 Plug the e...

Страница 7: ...ls by an electrically skilled person to ensure that they are functioning properly This requirement is deemed to be satisfied for normal and environmental conditions if the test intervals mentioned in...

Страница 8: ...CTBC120 when I n 100 mA 330 A CTBC120P when I n 100 mA 630 A CTBC210 when I n 300 mA 630 A CTBC210P when I n 100 mA 630 A CTBC210P when I n 300 mA 1000 A Measurement accuracy 1 of full scale value Te...

Отзывы: