Technical data VMD461
72
VMD461_D00314_01_M_XXEN/10.2018
IC2/(IC3…6).......................................................................................................................................................... 400 V
IC3/(IC4…6).......................................................................................................................................................... 400 V
IC4/(IC5…6).......................................................................................................................................................... 400 V
IC5/IC6....................................................................................................................................................................... 4 kV
Protective separation (reinforced insulation):
IC1/(IC3…6)................................................................................................DC, 3AC: Overvoltage category III, 1250 V
.................................................................................................................. 1AC, 3NAC: Overvoltage category III, 1000 V
IC2/(IC3…6).......................................................................................................................................................... 300 V
IC3/(IC4…6).......................................................................................................................................................... 300 V
IC4/(IC5…6).......................................................................................................................................................... 300 V
IC5/IC6..................................................................................................................................................................... 300 V
Voltage test (routine test ) acc. to IEC 60255-27/DIN EN 50178:1998
IC2/(IC3…6)....................................................................................................................................................... 2.21 kV
IC3/(IC4…6)....................................................................................................................................................... 2.21 kV
IC4/(IC5…6)....................................................................................................................................................... 2.21 kV
IC5/IC6.................................................................................................................................................................. 2.21 kV
Supply voltage
Nominal supply voltage
U
s
....................................................................................................................... 100…240 V
Tolerance
U
s
......................................................................................................................................................... ±25 %
Nominal frequency range
U
s
..................................................................................................................... DC, 50/60 Hz
Power consumption at AC 230 V..................................................................................................... < 3.5 W/ < 7.5 VA
maximum ................................................................................................................................. 3.5 W / 9 VA
Measuring circuit
VMD461
System type .....................................................................................................................................DC, 1AC, 3AC, 3NAC
Nominal voltage
U
n
(L-N) ..................................................................................................................................... AC 50…260 V
(L-L)...................................................................................................................................... AC 87…450 V
(DC+ / DC–)........................................................................................................................ DC 50…450 V
Measuring range........................................................................................................................................0…1.15 x
U
n
Overload capacity............................................................................................................................... 1.5 x
U
n max
for 5 s
Response values.............................................................................................................................................1…150 %
Operating uncertainty
U
n
................................................................................................................................... ≤ ±1 %
Содержание LINETRAXX VMD461
Страница 6: ......
Страница 40: ...Operation and configuration 40 VMD461_D00314_01_M_XXEN 10 2018 ...
Страница 66: ...Menu 66 VMD461_D00314_01_M_XXEN 10 2018 ...
Страница 80: ...Technical data VMD461 80 VMD461_D00314_01_M_XXEN 10 2018 ...
Страница 83: ......