Modbus register assignment of the ISOMETER®
49
isoMIL425_D00203_03_M_XXEN/03.2019
3016
RW
Baud rate "Adr 1"
UINT 16
---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
3017
RW
Parity "Adr 2"
UINT 16
---
0 = 8N1
1 = 8O1
2 = 8E1
3 = 8N2
3018
RW
Start-up delay "t"
during device
start
UINT 16
s
0 …10
3019
RW
Response delay
"ton" for relays
"K1" and "K2"
UINT 16
s
0 … 99
3020
RW
Delay on release
"toff" for relays
"K1" and "K2"
UINT 16
s
0 … 99
3021
RW
Repetition time
"test" for
automatic
device test
UINT 16
---
0 = OFF
1 = 1h
2 = 24 h
3022
RW
Parameter "Z":
Activation of
Z mode for
impedance
calculation
UINT 16
---
0/1 *
Register
Permissions
Description
Format
Unit
Value range