iso415R-x_D00401_00_M_XXEN / 04.2021 29
ISOMETER® iso415R
Connection
Connection type ..............................................................Push-in
Nominal current ...............................................................
≤
10 A
Connection properties
rigid ............................................0.2…1.5 mm² (AWG 24…16)
flexible .......................................0.2…1.5 mm² (AWG 24…16)
with ferrule ..................................................... 0.25…0.75 mm²
with ferrule
4)
....................................................... 1.0…1.5 mm²
Environment/EMC
EMC ...................................................................... IEC 61326-2-4
Ambient temperatures
Operation ..............................................................-25…+55 °C
Transport ..............................................................-40…+85 °C
Storage ................................................................. -40…+70 °C
Classification of climatic conditions acc. to IEC 60721
(ex-
cept condensation and formation of ice)
Stationary use (IEC 60721-3-3) ...........................................3K23
Transport (IEC 60721-3-2) ...................................................2K11
Long-term storage (IEC 60721-3-1) .................................... 1K22
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ...........................................3M11
Transport (IEC 60721-3-2) ................................................... 2M4
Long-term storage (IEC 60721-3-1) .................................. 1M12
Other
Operating mode ....................................... continuous operation
Mounting ................. cooling slots must be ventilated vertically
Degree of protection, internal components (DIN EN 60529) IP30
Degree of protection, terminals (DIN EN 60529) ..................IP20
Enclosure material ................................................ polycarbonate
DIN rail mounting acc. to ........................................... IEC 60715
Flammability class ....................................................... UL94 V-0
Documentation number ...................................................D00401
Weight ............................................................................≤ 100 g
()*
Factory setting
1)
Can be parameterised via app and Modbus
2)
When supplied by or when monitoring systems with a frequency
≥
200 Hz, the cable must be laid in a shockproof manner.
3)
Refers to relays that have not been operated with high contact cur-
rents
4)
Use crimping pliers similar to CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
only.
5)
Factory setting: 100 + last two digits of serial number
6)
Resolution/step size 1 kΩ
7.1
Standards & certifications
Devices of the iso415R series have been devel-
oped according to the following standards:
•
IEC 61557-8
7.2
Ordering information
Supply voltage
U
S
Type
Art. No.
AC/DC
DC
24 V
iso415R-24
B71602000
100…240 V
iso415R-2
B71603000