Operation and setting
56
IRDH375_D00124_05_M_XXEN/01.2020
6.5 Menu ISO ADVANCED: Setting of the extended
functions
6.5.1 External coupling devices (AGH: no)
Basic setting "no", when no coupling device is used (factory setting).
AGH: 204 AK80
Terminal AK of the IRDH375 is connected to terminal AK80 of the
AGH204S-4. The nominal voltage range is extended to 3AC 0…1,650 V. Only
current converters with an output voltage not exceeding DC 1,000 V are al-
lowed to be connected (see "operation with coupling device" on page 40).
AGH: 520S
Terminal AK of the IRDH375 is connected to terminal 5 of the AGH520S. The
nominal voltage range is extended to AC 0…7,200 V. Only current converters
with an output voltage not exceeding DC 1,000 V are allowed to be connect-
ed.
AGH: 204 AK160
Terminal AK of the IRDH375 is connected to terminal AK160 of the
AGH204S-4. The nominal voltage range is extended to 3AC 0…1,300 V. Only
current converters with an output voltage not exceeding DC 0…1,840 V are
allowed to be connected (see "operation with coupling device" on page 40).