6.4 Taking over or returning the Master function
Certain commands in a BMS network can only be carried out when the FTC470XMB takes over the
Master function. This is required for the parameterization of BMS devices, for example.
When BMS address 1 is continuously assigned to the FTC470XMB , taking over of the Master function
is not necessary.
6.4.1 Taking over the Master function
Writing to FTC470XMB (= output data of the Modbus RTU Master)
Table 6.11: Master request: taking over of the Master function by FTC470XMB
Reading from
FTC470XMB (= input data of the Modbus RTU Master)
Table 6.12: FTC reply to: taking over of the Master function by FTC470XMB
Taking over of the Master function is
not
required for requesting alarm and operating messages, meas-
uring values and in case of control functions for EDS systems.
The FTC470XMB
must
take over the Master function in case of parameter re-
quests and new parameter settings!
Take into account that the Master function must be returned by the FTC470XMB
after taking over the Master function and the subsequent parameterization.
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
channe
l No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Command to FTC470XMB to take over the
Master function in the BMS network tempo-
rarily. After carrying out this command, the
FTC470XMB is ready to output further com-
mands to the BMS network.
FTC470...,
FTC470XMB
address
0
0
112
0
2
0
FTC470XMB has taken over the Master func-
tion. The taking over is acknowledged by the
old Master by answering already as a Slave.
Address
0
0
112
0
2
0