The FTC470XMB protocol converter
14
4.2.1
DIP switch for Modbus RTU address setting
The appropriate addresses are set using BCD numbers between 1 an 127.
Selecting Modbus address 0, with all DIP switches in position OFF, would be an invalid ad-
dress which is not allowed
!
The FTC470XMB must be disconnected from the supply after changing the DIP
switch settings. Reconnection to the power supply provides the actual indica-
tion of the Modbus RTU status.
DIP switch of the Modbus group in
down
position means binary 1
DIP switch of the BMS group in
up
position means binary 0
Address DIP switch
Dec. addr.
1
2
3
4
5
6
7
1
0
0
0
0
0
0
1
2
0
0
0
0
0
1
0
3
0
0
0
0
0
1
1
4
0
0
0
0
1
0
0
5
0
0
0
0
1
0
1
6
0
0
0
0
1
1
0
7
0
0
0
0
1
1
1
8
0
0
0
1
0
0
0
..
..
..
..
..
..
..
..
...
...
...
...
...
...
...
...
127
1
1
1
1
1
1
1
ON
ON
ON
1
1 2 3 4 5 6 7 8
1 2 3 4
A6 A5 A4 A3 A2 A1 A0
ADDRESS MODBUS