5. Installation
5.1 Basic configuration
Before installing the FTC470XDP, an address must be assigned to it. The BMS bus and the PROFIBUS
DP must also be provided with an address.
1. At first, consult the person in charge of the electrical installation for the address assignment of
the protocol converter in the respective bus structures. Therefore, it is necessary to find out
whether the FTC470XDP can be operated as BMS Master (basic setting).
2. Set the appropriate BMS address (1 to 30; 1 = Master) by means of the DIP switch using binary
digits. Address 5 corresponds to the following switch positions, for example:
A4 = 0 A3 = 0 A2 = 1 A1 = 0 A0 = 1
Factory setting = 1
Table 5.1: BMS bus address table
Double assignment of addresses may lead to serious malfunctions in the BMS
or PROFIBUS DP networks concerned.
Dez.
Addr.
A4
A3
A2
A1
A0
Dez.
Addr.
A4
A3
A2
A1
A0
1
0
0
0
0
1
16
1
0
0
0
0
2
0
0
0
1
0
17
1
0
0
0
1
3
0
0
0
1
1
18
1
0
0
1
0
4
0
0
1
0
0
19
1
0
0
1
1
5
0
0
1
0
1
20
1
0
1
0
0
6
0
0
1
1
0
21
1
0
1
0
1
7
0
0
1
1
1
22
1
0
1
1
0
8
0
1
0
0
0
23
1
0
1
1
1
9
0
1
0
0
1
24
1
1
0
0
0
10
0
1
0
1
0
25
1
1
0
0
1
11
0
1
0
1
1
26
1
1
0
1
0
12
0
1
1
0
0
27
1
1
0
1
1
13
0
1
1
0
1
28
1
1
1
0
0
14
0
1
1
1
0
29
1
1
1
0
1
15
0
1
1
1
1
30
1
1
1
1
0
Содержание FTC470XDP
Страница 10: ...Safety instructions 10 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 22: ...The FTC470XDP protocol converter 22 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 26: ...Installation 26 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 79: ......