Operation
38
EDS...-L: All alarm LEDs light up.
Once the test has been completed, all LEDs must go out again, with the
exception of the "ON" LED.
6.3.4
Resetting saved alarm messages (RESET)
If the fault memory is enabled, the alarm status will remain, even after
the cause of the fault has been eliminated, until a "RESET" is carried out.
Press the "ESC" key to exit the display of the current alarm message. To
carry out a RESET:
press the "RESET" button on the front panel of the EDS... ,
press the external RESET button connected to the EDS... ,
send a RESET command via the BMS bus.
EDS...-D only: calling the "RESET" function in the Control menu.
Stored alarm messages that are no longer pending are reset, the alarm
relay drops out, the ALARM LEDs go out and there are no longer any
alarm messages on the BMS bus. The EDS...-D shows the progress of the
reset operation.
TEST 12/12
Insulation fault
50 mA
Addr.: 2 Channel: 12