Operation
35
6.2.4
Resetting saved alarm messages (RESET)
If the fault memory is enabled, the alarm status will remain, even after
the cause of the fault has been eliminated, until a "RESET" is carried out.
Press the "ESC" key to exit the display of the current alarm message. A
reset is carried out by:
pressing the "RESET" button on the front panel of the EDS460-DG,
pressing an external reset button connected to the EDS460-DG,
sending a reset command via the BMS bus.
calling up the "RESET" function in the Control menu.
Stored alarm messages that are no longer pending are reset, the alarm
relay drops out, the ALARM LEDs go out and there are no longer any
alarm messages on the BMS bus. The EDS460-DG shows the progress
of the reset operation.