Basic programs
63
VMD460-NA_D00001_05_M_XXEN/01.2020
Explanatory notes to "0126" settings
1)
Relay mode:
NC:
The relay is
energised
in
normal operation
and deenergised in the alarm state
NO
:
The relay is
deenergised
in
normal operation
and energised in the alarm state
2)
Not used for CEI 0-21(:2012-06, :V1:2012-12, :V2:2013-12, :2014-09,
:V1:2014-12)
8. Dig. input
D1: K1
D2: K2 (backup)
D3: local control
D4: external signal
Exit
1. Mode
NC; NO; off
D1: NC
D2: off
D3: NO
D4: NO
2. t
(START-UP)
40 ms…60 min
D1: 500 ms
D2: ––
D3; D4: ––
2)
3. Fault memory
off; on
D1: off
D2: off
D3; D4: ––
2)
CEI 0-21 menu:
once twice
Factory
setting