ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 85
ATICS-2-63A-ISO
8.1.2 Messages with error code or service code
Error code/service
code
Description
Action
1.xx, 4.xx, 9.xx
Fault message from the internal memory
monitoring.
• Contact the Bender service.
3.10
Prewarning
The max. number of operating hours will be
reached in one year
• For functional safety SIL 2 require-
ments according to IEC 61508-2,
the replacement must be planned.
Alarm can be acknowledged (see
chapter „Reset menu 3: Changeo-
ver“ on p. 59)
3.11
Maximum number of operating hours
exceeded for functional safety according to
IEC 61508-2:2010.
• For functional safety SIL 2 require-
ments according to IEC 61508-2, the
replacement must be carried out.
Alarm can be acknowledged
• (see chapter „Reset menu 3: Change-
3.12
Maximum number of changeovers
exceeded.
• Plan device replacement. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
59)
3.13
Changeover due to overcurrent or short
circuit detected. These changeovers reduce
the life of the device. Currents exceeding
130 A are considered to be overcurrents or
short-circuit currents.
• Have qualified personnel assess the
short-circuit load.
Contact the Bender service. Alarm
can be acknowledged (see chapter
„Reset menu 3: Changeover“ on p.
59)
3.50
Service alarm has been reset. Only displayed
in the service logger menu.
• No action required.
4.61...4.66
Switch state error: Deviation between the
target position of the switching logic and
the reported position. This error occurs
when the required input voltage is detected
to have failed during the changeover.
• Reset, perform test changeover. If
no error is displayed: OK
• Check supply voltage or current
limitation (17 A are required for
switching)
• If error continues to exist: Replace
device immediately
6.xx, 7.xx, 8.1x
Device error. The internal self monitoring of
the device has detected a fault which could
impair the safe operation of the device.
• Replace device immediately.
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...