Technical data IRDH275(B)
68
Status number
Value of the respective number
P
os
iti
on
of numbers from the left
0 =
1 =
2 =
3 =
4 =
1
K1: N/O operation Test
K1: N/C operation Test
K1: flashing function
K1: N/O operation
K1: N/C operation
2
K2: N/O operation Test
K2: N/C operation Test
K2: flashing function
K2: N/O operation
K2: N/C operation
3
no external coupling
AK AGH204S 80K
AK AGH520S
AK AGH204S 160K
AK AGH150W 160K
4
Cemax 1 μF **
Cemax 10 μF **
Cemax 150 μF
Cemax 500 μF
5
6
Self test every 24 hours
Self test every hour
no periodic self test
7
Language German
Language English
8
Password protection not
activated
Password protection
activated
9
AMP measuring
principle
DC measuring principle
10
max. filter frequency
0.1Hz **
max. filter frequency 1Hz
**
max. filter frequency
10Hz **
max. filter frequency
50Hz **
11
min. filter frequency
0,1Hz **
min. filter frequency 1Hz
**
min. filter frequency
10Hz **
min. filter frequency
50Hz **
12
BMS mode **
Isodata **
test data **
13
Bus address in the tens
place IRDH275
Value: 5 ... 9
14
Bus address in the units
place IRDH275
Value: 5 ... 9
15
Number of pulses 2-9 **
Value: 5 ... 9
** The parameters marked with two asterisks are settable via the Service menu item! A password is required for that
purpose !