background image

2.4

VENTILATION REQUIREMENTS

Detailled recommendations for air supply
are given in BS5440:2. The following notes
are for general guidance:
– It is not necessary to have a purpose

provided air vent in the room or
compartment in which the appliance is
installed.

2.5

GAS SUPPLY

– The gas installation should be in

accordance with BS6891. The gas
required for the boiler is specified in
section 1.3.

– Ensure that the pipework from the meter

to the appliance is of adequate size.

– The governor at the meter must give a

constant outlet pressure of 20 mbar (8
inwg) for natural gas and 30 - 37 mbar
(12 - 15 inwg) for LPG, when the
appliance is running.

– The gas supply line should be purged.

NOTE: Before purging open all doors
and windows, also extinguish any
cigarettes, pipes, and any other naked
flames.

– The complete installation must be tested

for gas soundness.

2.6

ELECTRICITY SUPPLY

The appliance MUST be earthed. A mains
supply of 230 V - 50 Hz single phase is
required. All external controls and wiring
MUST be suitable for mains voltage.

Wiring should be in 3 core PVC insulated
cable NOT LESS than 0.75 mm

2

(24 x 0.2

mm) to BS6500, Table 16. Wiring external
to the boiler MUST be in accordance with
current l.E.E. Wiring Regulations (BS 7671)
and local regulations. 
The supply connection to the flying lead
provided MUST be made to a fused double
pole switch, having a 3 mm (1/8 in) contact
separation in both poles, serving only the
boiler and system controls; the fuse rating
should be 3 amp. 
This connection should be readily accessible
and be made adjacent to the boiler (except
in the case of bathroom installations for
domestic boilers where the point of
connection to the mains MUST be outside
of the bathroom).

2.7

EXTERNAL CONTROLS

(Refer to section 2.8.1)

The boiler is intended for use with a 24 V
room thermostat. The connection is made
inside the control box as described in
section 3.9.

2.8

WATER SYSTEMS - GENERAL

– This appliance is designed for connection

to sealed central heating water systems.

– Check that the mains water pressure is

sufficient to produce the required D.H.W.
flow rate, but does not exceed the
maximum D.H.W. pressure (1.3 point).

Where mains pressure exceed 6 bar a
pressure reducing valve must be fitted
in the D.H.W. inlet.

2.8.1

Treatment of water 
circulating systems

– All recirculatory systems will be subject

to corrosion unless an appropriate water
treatment is applied. This means that the
efficiency of the system will deteriorate
as corrosion sludge accumulates within
the system, risking damage to pump and
valves, boiler noise and circulation
problems.

– For optimum performance after

installation this boiler and its associated
central heating system must be flushed
in accordance with the guidelines given in
BS 7593 “Treatment of water in
domestic hot water central heating
systems”.

– Sime ltd recommend  only the use of

FERNOX products for flushing and water
treatment. This particularly important in
hard water areas.

Failure to flush and add inhibitor to the
system may invalidate the appliance
warranty. Artificially softened water

must not be used to fill the heating
system.

– It is important to check the inhibitor

concentration after installation, system
modification and at every service in
accordance with the manufacturer’s
instructions. (Test kits are available from
inhibitor stockists).

2.9

REQUIREMENTS 
FOR SEALED 
WATER SYSTEMS

The heating system design should be based
on the following information:

a) The available pump head is given in fig. 5.
b) The burner starts when the C.H. flow

reaches 400÷450 l/h. This safety
condition is ensured by the flow switch.

c) The appliance is equipped with an internal

by-pass that operates with system heads
(H) greater than 3 m. The maximum flow
through the by-pass is about 300 l/h. If
thermostatic radiator valves are to be
installed, at least one radiator should be
without a thermostatic valve (usually the
bathroom radiator).

d) A sealed system must only be filled by a

competent person using one of the
approved methods shown in fig. 7. The
system design should incorporate the
connections appropriate to one of these
methods.

0

200

1600

1400

1200

1000

800

600

400

PORTATA (l/h)

PREV

ALENZA RESIDU

A (mbar)

500

400

100

200

300

30

20-25

Me

tr

opolis DGT

600

30

20-25

By-pass inserito

By-pass escluso

FLOW RATE

(l/sec)

A

V

AIL

ABLE HEAD

(mbar)

Fig. 5

By-pass ON
By-pass OFF

11

ENG

IT

ES

Содержание Metropolis DGT 25 BF

Страница 1: ...lation and servicing instructions ENG IT ES ENSURE THAT THESE INSTRUCTIONS ARE LEFT FOR THE USER AFTER COMPLETION OF THE BENCHMARK SECTION Please read the Important Notice within this guide regarding...

Страница 2: ...e recommended Avoid direct contact with sharp edges Avoid contact with any hot surfaces NOTICE Please be aware that due to the wet testing of the appliance there may some residual water in the hydraul...

Страница 3: ......

Страница 4: ...dards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimi se safety efficiency and performance Benchmark is managed and p...

Страница 5: ...the Benchmark Checklist in the use and maintenance section of this manual been completed IPX5D Important Information IT IS A STATUTORY REQUIREMENT THAT ALL GAS APPLIANCES ARE INSTALLED BY COMPETENT P...

Страница 6: ...y water systems and is supplied fully assembled and equipped with complete valve packs The boiler can be used with a 24V room thermostat class II according to EN 60730 1 This booklet provides instruct...

Страница 7: ...perature C 100 125 Smokes flow gr s 16 16 Losses after shutdown to 50 C W 73 Category II2H3 Type B22P 52P C12 32 42 52 82 Electrical supply 230V 50 hz fused at 3 A Internal fuse Line F1 6AT Weight kg...

Страница 8: ...Combustion chamber 6 Gas valve 7 Water pressure valve 8 Circulator with air release vent 10 Hydrometer 11 Expansion vessel 12 D H W flow meter 13 By pass 14 D H W filter 15 Boiler discharge 16 3 BAR...

Страница 9: ...s that set the burner output is reduced When this set temperature is reached the burner extinguishes and the fan stops The pump continues to run for 30 seconds to prevent residual heat build up in the...

Страница 10: ...ided it is modified accordingly Where installation will be in an unusual location special procedures may be necessary BS6798 gives detailed guidance on this aspect 2 3 FLUE TERMINAL POSITION Detailed...

Страница 11: ...W flow rate but does not exceed the maximum D H W pressure 1 3 point Where mains pressure exceed 6 bar a pressure reducing valve must be fitted in the D H W inlet 2 8 1 Treatment of water circulating...

Страница 12: ...12 ENG IT ES TYPICAL SYSTEM DESIGN NOTE A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance Fig 6 Fig 7 ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM...

Страница 13: ...rim flushing type the outlets are shrouded and it is impossible to attach a temporary hand held spray no anti syphonage device is necessary 2 11 FILLING THE WATER SYSTEM Open the C H flow and C H ret...

Страница 14: ...duct is longer than 1 metre it is advisa ble to insulate the duct in order to avoid the formation of dew on the outside of the pipe when the weather is particularly cold With ducts with discharge posi...

Страница 15: ...horizontal pipe 80 x 0 20 1 40 7 meter horizontal pipe 80 x 0 30 2 10 No 2 90 elbows 80 x 0 35 0 70 No 2 90 elbows 80 x 0 40 0 80 No 1 wall terminal 80 0 15 0 50 Total head loss 2 25 3 40 5 65 mm H2O...

Страница 16: ...he boiler casing remove the two securing screws and tilt the control panel Connect the thermostat to the 6 pole ter minal board as indicated in the boiler elec trical diagram see diagram 2 19 after ha...

Страница 17: ...SSO RED FLM VERDE GREEN ARANCIO ORANGE VCC GND OUT ROSSO RED ROSSO RED ROSSO RED 3 3 VDC 24 VDC 3 3 VDC 3 3 VDC 24 VDC 3 3 VDC 24 VDC 17 VDC 12 VDC 24 VDC R59 Fig 11 KEY F Fuse 1 6 AT TRA Ignition tra...

Страница 18: ...T is only available if a resettable anomaly is signalled D H W SET Press the key to display the D H W temperature value set HEATING SET Press the key to display the heating temperature value set value...

Страница 19: ...03 17 Pump heating activation delay 0 99 10 sec 1 01 18 Re ignition delay 0 10 Min 1 03 19 Modulation D H W flowmeter Disabled 01 1 Enabled 29 Anti legionella only D H W tank Disabled C 1 50 80 PARAME...

Страница 20: ...nition failure with consequent activation of block can be due to Lack of gas The ignition electrode persists in dischar ging for max 10 seconds If the burner does not ignite the anomaly is signalled T...

Страница 21: ...NTILATORE CAMERA STAGNA Fig 14 SEALED CHAMBER FAN PRESSURE SWITCH A B C RIFERIMENTO POSIZIONE BY PASS D Fig 15 KEY A By pass on B By pass off C Water pressure valve D Automatic air vent E Drain vent R...

Страница 22: ...ws fig 18 Connect the column or a manometer to the intake down stream of the gas valve and disconnect the valve VENT pressure test point tube 5 fig 16 Remove the cap 1 from the modulator Connect the c...

Страница 23: ...manifold unit Ideally use a vacuum clea ner and a soft brush so as to remove any dust particles that may have accumulated take care not to damage the insulation Clean the heat exchanger removing any...

Страница 24: ...05 FLAME LOCKOUT ALARM 06 fig 20 a If the flame control has not detected the presence of the flame after a complete ignition sequence or for any other rea son the card cannot see the flame the boiler...

Страница 25: ...general once a year should be adequate It is the law that a competent person such as a Gas Safe Register registered engineer must carry out any service work 4 7 1 Combustion Check Incorporated into t...

Страница 26: ...ot affect the customer s statutory rights If yes and if required by the manufacturer has a water scale reducer been fitted CONDENSING BOILERS ONLY The condensate drain has been installed in accordance...

Страница 27: ...er No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date...

Страница 28: ...e the position of the sensing pipe and disconnect 6 REPLACEMENT OF PARTS If an electrical fault occurs on the appliance the preliminary electrical system checks must be carried out first When any serv...

Страница 29: ...iler cover see 4 3 Close the flow and return isolation valves Drain the boiler using the fitted drain vent see fig 15 Disconnect the electrical connections to the pump Remove the four fixing screws Re...

Страница 30: ...Water heat exchanger 014 6231362 NTC sensor 015 6318600 Sealed chamber front panel 016 6225636 Fan 017 6317900 Combustion chamber front panel 018 6318700 Combustion chamber side insulat 019 6264841 C...

Страница 31: ...valve operation 062 6319630 Flowmeter 063 6147231 Straight fitting 1 2 15 064 6245000 Ball cock 3 4 x22 065 6245001 Ball cock 1 2 x15 066 6063601 Gas cock 1 2 068 2030227 Gasket 12x18x2 069 6226457 O...

Страница 32: ...4258 Gas Water heat exchanger 014 6231362 NTC sensor 015 6318600 Sealed chamber front panel 016 6225636 Fan 017 6317900 Combustion chamber front panel 018 6318700 Combustion chamber side insulat 019 6...

Страница 33: ...9630 Flowmeter 063 6147231 Straight fitting 1 2 15 064 6245000 Ball cock 3 4 x22 065 6245001 Ball cock 1 2 x15 066 6063601 Gas cock 1 2 068 2030227 Gasket 12x18x2 069 6226457 O ring 12bis diam 16x1 90...

Страница 34: ...34 ENG IT ES NOTES...

Отзывы: