3. Fit the 1000mm long concentric pipe to the 
first to extend the flue into the roof space using 
the clamps provided at each joint and ensure 
the inner flue joint is pushed fully home.

4. Fit the concentric air inlet in the roof space, 
see diagram opposite. If terminating the air inlet 
at low level, ensure it is at least 300mm above 
the top surface of any roof insulation.

Note : 

It is important that the air inlet is always 

kept  clear  and  if  possible  this  should  not 
terminate adjacent to the roof access hatch.

5. Measure and cut, (if necessary) the first single 
flue  pipe  away  from  the  concentric  flue/air 
inlet,  slip  supports  onto  pipes  as  required 
(see  the  diagram  in  3.0  Design/Technical  for 
typical details), before pushing home firmly the 
deburred pipe end into the pipe socket. When 
making a joint, mark the socket depth on the 
plain end of pipe and check the mark to ensure 
the joint is pushed home fully.

6. Repeat the above procedure for any further 
pipes/bends etc. until the pipework extends to 
the ridge terminal, (temporarily support/secure 
the pipe if necessary).

7.  Connect  the  60mm  diam.  single  flue  pipe 
to  the  ridge  terminal  using  the  60  x  80mm 
adaptor provided. Ensure the vertical pipework 
is adequatley supported at the connection to 
the ridge terminal. 

8.  Visually  inspect  and  check  each  joint  is 
pushed home fully. Ensure the flue also has a 
minimum continuous fall back to the boiler of 
50mm/metre.

9. Permanently secure the concentric and single 
flue  pipes  at  approximately  1  metre  centres. 
Ensure a bracket is provided adjacent to each 
joint on horizontal pipes.

Note : 

The flue pipe must 

not

 rely on the ridge 

terminal for support.

4.0 INSTALLATION

Pull terminal down while

securing straps to the battons

25mm gap min.

or metal batten

Fixing straps secured

to roof battons

Weather Cap

Page 9

GULFSTREAM 

A-CL

ASS

RIDGE TERMINAL FLUE KIT

RIDGE TERMINAL FLUE KIT

Содержание GulfStream A-CLASS

Страница 1: ...GAS SAFETY INSTALLATION AND USE REGULATIONS In your own interest and that of safety it is law that all gas appliances are installed by competent persons and in accordance with the above regulations TM...

Страница 2: ...Page 2...

Страница 3: ...ntaining one of our products unless we have been specifically requested to do so All goods are sold subject to our Conditions of Sale which are set out at the rear of this manual In the interest of co...

Страница 4: ...ed as near as practical to the GulfStream A CLASS appliance and the route of the ue is checked and clear of any roof trusses or other obstructions in the roofspace The roof space or other suitable com...

Страница 5: ...Flue Kit 60 x 80 adaptor Ridge terminal If necessary the flue can be run using 87 90 bends with a continuous min fall of 50mm metre 5 3 2 T G t i K e u l F l a n i m r e T e g d i R d r a d n a t S y...

Страница 6: ...t length of ttings 1 x 90 bend x 1 9m 1 9m 2 x 45 bend x 1 5m 3 0m Total equivalent ue length 3 0 5 5 1 9 3 0 13 4m As long as the ue pipework always runs back to the boiler at a minimum fall of 50mm...

Страница 7: ...le If further information is required or if there is any doubt regarding the adequacy of combustion air supply Gledhill Technical Dept should be consulted Combustion air must not be drawn from within...

Страница 8: ...of at least 50mm metre back to the boiler and must not be allowed to dip i e fall below the horizontal or form a low point at which condensate could accumulate Theridgeterminalshouldbeinstalledasfoll...

Страница 9: ...plain end of pipe and check the mark to ensure the joint is pushed home fully 6 Repeat the above procedure for any further pipes bends etc until the pipework extends to the ridge terminal temporarily...

Страница 10: ...Page 10...

Страница 11: ...Page 11 GULFSTREAM A CLASS...

Страница 12: ......

Отзывы: