background image

10

 

INSTALLATION

PLUMBING CONNECTIONS

CENTERSTORE cylinders require the following
pipework connections.

• 

Cold water supply to and from inlet controls.

• 

Outlet to hot water draw off points. 

• 

Discharge pipework from valve outlets to

  

tundish

• 

Connection to the primary circuit.

All connections are 22mm compression. However, 
3/4”BSP parallel threaded fi ttings can be fi tted to 
the primary coil connections if required.

ELECTRICAL SU

PPLY (FIG. 7)

All units are fi tted with a 3kW immersion heater and 
a combined thermostat and thermal cut-out to con-
trol the indirect heating source. 

The CENTERSTORE 

cylinder MUST be earthed.

 

All wiring to the unit must be installed in  accordance 
with the latest IEE Wiring Regulations and the supply 
circuits must be protected by a suitable fuse and 
double pole isolating switch with a contact separa-
tion of at least 3mm in both poles. All connections 
are made to the terminal block located under the 
terminal cover mounted on the side of the unit. The 
supply cable(s) must be routed through the cable 
grip(s) in the terminal housing.

DISCONNECT FROM MAINS SUPPLY BEFORE 
REMOVING ANY COVERS. DO NOT

 

BYPASS THE 

THERMAL CUT-OUTS IN ANY CIRCUMSTANCES.

 

Ensure the thermostat and thermal cut-out sensing 
bulbs are pushed fully into the pockets on the ele-
ment plate assembly.

 

BOILER SELECTION

The boiler should have a control thermostat and non 
self-resetting thermal cut-out and be compatible 
with unvented storage water heaters.
Where use of a boiler without a thermal cut-out is 
unavoidable a “low head” open vented primary cir-
cuit should be used. The feed and expansion cistern 
head above the CENTERSTORE cylinder should not 
exceed 2.5m.

PRIMARY CIRCUIT CONTROL

The 2 port motorised valve supplied with the
 CENTERSTORE cylinder MUST be fi tted on the primary 
fl ow to the CENTERSTORE cylinder heat exchanger 
and wired in series with the indirect thermostat and 
thermal cut-out fi tted to the unit.
Primary circulation to the CENTERSTORE cylinder 
heat exchanger must be pumped;  gravity circulation 
WILL NOT WORK.

SPACE AND HEATING SYSTEMS CONTROLS

The controls provided with the CENTERSTORE 

cylinder will ensure the safe operation of the 

unit within the central heating system. Other 

controls will be necessary to control the space 

heating requirements and times that the system 

is required to function. (See Fig. 7)

The CENTERSTORE cylinder is compatible with 

most 

heating controls, examples of electrical

circuits are shown in Figs. 8 and 9. 

However, 

other systems may be suitable, refer to the 

controls manufacturers’ instructions, supplied 

with the controls selected, for alternative system 

wiring schemes

.

Содержание Centerstore 120

Страница 1: ...be stored in an upright position in an area free from excessive damp or humidity This appliance complies with the requirements of the CE marking directive and is Kiwa approved to show compliance with...

Страница 2: ...ON GENERAL 4 INSTALLATION 10 COMMISSIONING 12 MAINTENANCE 12 USER INSTRUCTIONS 13 FAULT FINDING AND SERVICING 14 OTHER INFORMATION 16 ENVIRONMENTAL INFORMATION 16 COMMISSIONING CHECK LIST 17 SERVICE R...

Страница 3: ...MINAL FITTINGS TAPS ETC The CENTERSTORE cylinder can be used with most types of terminal fittings It is advantageous in many mixer showers to have balanced hot and cold water supplies In these instanc...

Страница 4: ...ework be at least 1 metre below the level of the heater this can be achieved by attaching a hose to the drain tap outlet spigot EXPANSION VESSEL The expansion vessel accommodates expansion that result...

Страница 5: ...g 4 General dimensions Notes 1 Recovery time based on heating 70 of capacity through 45 C 2 Direct heating times assume use of lower element only from cold through 45 C Table 2 Dimensions and performa...

Страница 6: ...nt resistance length should be at least two sizes larger than the nominal outlet size of the safety device between18and27matleast3sizeslarger and soon Bendsmustbetakenintoaccountincalculating the flow...

Страница 7: ...f 28mm pipe D2 from a G1 2 temperature relief valves equates to 18m Subtract the resistance of 4 No 28mm elbows at 1 0m each 4 0m Therefore the maximum permitted length equates to 14m As the actual le...

Страница 8: ...R BEND G 1 2 15MM 22mm 28mm 35mm UP TO 9M UP TO 18M UP TO 27M 0 8M 1 0M 1 4M G 3 4 22MM 28mm 35mm 42mm UP TO 9M UP TO 18M UP TO 27M 1 0M 1 4M 1 7M G 1 28MM 35mm 42mm 54mm UP TO 9M UP TO 18M UP TO 27M...

Страница 9: ...NOT SUPPLIED PRIMARY RETURN PRIMARY FLOW ELEMENT CONTROLS HOUSING INLET SECONDARY RETURN TAPPING IF REQUIRED NOT SUPPLIED COLD WATER COMBINATION VALVE 2 PIECE BALANCED COLD WATER CONNECTION IF REQUIRE...

Страница 10: ...out sensing bulbs are pushed fully into the pockets on the ele ment plate assembly BOILER SELECTION Theboilershouldhaveacontrolthermostatandnon self resetting thermal cut out and be compatible with un...

Страница 11: ...11 Fig 8 Schematic wiring diagram Basic 2 x 2 port valve system Fig 9 Schematic wiring diagram 3 port mid position valve system N B Must be used in conjunction with 2 port zone valve supplied...

Страница 12: ...llow the CENTERSTORE cylinder to heat up to a normal working temperature 60o C recommended approximately graduation 4 on the thermostat If necessary the temperature can be adjusted by insertingaflatbl...

Страница 13: ...SEL CHARGE PRESSURE Remove the dust cap on top of the vessel Check the charge pressure using a tyre pressure gauge The pressure withsystemde pressurised shouldbe3 5bar If it is lower than the required...

Страница 14: ...ERATIONAL FAULTS Operational faults and their possible causes are detailed in the Fault Finding section of this book It is recommended that faults should be checked by a competent installer The air vo...

Страница 15: ...3 5 ba r 95 6 0 7 0 29 Te mpe ra ture Pre ssure R e lie f Va lv e 95 6 0 5 8 10 Ex pa nsio n v e sse l 1 2 litre 12 0 a nd 1 5 0 litre mo de ls 95 6 0 7 8 63 Ex pa nsio n v e sse l 1 8 litre 1 7 0 a n...

Страница 16: ...bing c onnec tions to m otoris ed valve s ee Fig 7 1 INTE RM ITTE NTLY E x pans ion V es s el c harge pres s ure has reduc ed below 3 5bar 1 S ee M aintenanc e s ec tion for re c harging proc edure 2...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...n used for the storage of potable water It has not been tampered with or been subjected to misuse or neglect The damage is not scale related Within 60 days of installation the user completes and retur...

Страница 20: ...eserve the right to change specifications and guarantee terms and conditions without notice For all technical support replacement parts and service issues please contact CENTERSTORE Brooks House Coven...

Отзывы: