19
Quick Installation Guide for solar inverter RPI M50A_12s V1 EU EN 5013237400 00 2016-04-11
Baud rate for RS485
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press the
ESC
button to open the main menu.
Otherwise, press the
ESC
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the buttons
and
to select the entry
General Settings
and press the
ENT
button.
Baud rate
Date & Time
Language
3.
Use the buttons
and
to select the
Baud rate
button and press the
ENT
but-
ton.
38400
19200
9600
4.
Press the
and
buttons to configure the value and press the
ENT
button.
Inverter ID
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press the
ESC
button to open the main menu.
Otherwise, press the
ESC
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the buttons
and
to select the
Installation Settings
button and press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the buttons
and
to configure the individual numbers.
Press the
ENT
button to confirm a number.
Grid Settings
Country
Insulation
Inverter ID: 001
4.
Use the buttons
and
to select the entry
Inverter ID
and press the
ENT
but-
ton.
ID=001
Setting ID:
5.
Press the
and
buttons to configure the value and press the
ENT
button.