44
Requirements
4.1
Requirements on the location
• Never use combustible building materials for the fireplace.
• Do not install the appliance against a flammable rear wall.
• Install a nonflammable insulation plate of at least 12 mm between the appliance and
the rear wall. The insulation plate must cover the entire area of the rear of the
appliance.
• The appliance must be installed approximately 2 cm from the rear wall.
• If the fire burns in the appliance, make sure that the floor temperatures below and in
front of the appliance cannot be higher than 85 °C .
• Make sure that the room where the appliance is installed is properly ventilated.
4.2
Requirements on the convection package (option)
• The convection outlet opening must be at least 1 meter above the appliance.
• No flammable material is present within 30 cm on both sides and 50 cm above the
convection outlet opening.
• The convection outlet opening must be at least 30 cm below the ceiling.
4.3
Other requirements
• The gas supply connection is near the operating unit for an easy connection.
• Only use gas piping of at least 1/2" and a shut-off valve to connect the gas supply to
the gas regulator block of the appliance.
• Install the fireplace on a solid floor that can bear the weight of the appliance and the
fireplace.
• If the floor is made of flammable material, take correct safety measures. Install a
temperature protection plate made of nonflammable material between the appliance
and the floor.
• The appliance must be a built-in appliance in a new fireplace or against a wall with the
wall support frame.
• If the concentric flue system is installed in a chimney that is used for wood or coal fire,
clean the chimney.
• If you built a new fireplace, make sure that it is ventilated with vents at the bottom and
top of the fireplace. If the fireplace is not ventilated the temperature of the appliance
can increase to dangerous temperatures and damage the fireplace.
4.4
Requirements on the outlet
4.4.1
Requirements on the roof outlet
Make sure that the outlet is installed at least 0.5 meter from the edge of the roof.
Note:
All the minimum distances are guidelines. Consult your national and local
directives for the exact minimum distances.
Location of any of the items(*)
Minimum distance between the items
and the roof outlet
At the same roof as the outlet
3 m
At a different roof as the outlet
1 m
Requirements
8
Room divider Large 3
Содержание Room Divider Large 3 CF
Страница 25: ...5 5 4 Roomdivider Large 3 with wall support frame Technical specification Room divider Large 3 25...
Страница 26: ...5 5 5 Roomdivider Large 3 left without frame Technical specification 26 Room divider Large 3...
Страница 28: ...5 5 7 Roomdivider Large 3 left hidden door 10 cm frame Technical specification 28 Room divider Large 3...
Страница 29: ...5 5 8 Roomdivider Large 3 right without frame Technical specification Room divider Large 3 29...
Страница 31: ...5 5 10 Roomdivider Large 3 right hidden door 10 cm frame Technical specification Room divider Large 3 31...
Страница 95: ...Available components for the concentric flue system Room divider Large 3 9 95...
Страница 96: ...Y Your Bellfires dealer 002 14 06 2019 348550...