5902 Bell 202 Modem Hardware Manual
October 19, 2007
9
4
Installation
The installation of the 5902 modem requires mounting the modem on the 7.5mm by 35mm DIN rail
and connecting the 5902 modem to the system I/O Bus. Refer to the
System Configuration Guide
,
at the beginning of this manual, for complete information on system layout, I/O Bus cable routing
and 5902 modem installation.
4.1
Connecting the Modem
The 5902 modem is normally connected to the SCADAPack I/O Bus through the I/O Bus
Connectors as shown in
figure 1
.In this configuration the SCADAPack provides a modem reset
(/RST) signal and a signal to enable the leds (LEDON) on the 5902 modem.
The 5902 modem is also available in a stand alone (SA) configuration. In this configuration the
5902 is not connected to a SCADAPack controller and the modem reset (/RST) signal and a signal
to enable the leds (LEDON) on the 5902 modem are not available. Two jumpers, J1 and J2, are
included to enable these signals on the 5902SA modem.
Figure 1: 5902 Module Layout
shows the
location of the jumpers.
5902 Modem
Remove jumper at J1 (/RST).
Remove jumper at J2 (LEDON).
5902SA Modem
Install jumper at J1 (/RST).
Install jumper at J2 (LEDON).
Status LEDs
I/O Bus
Connector
I/O Bus
Connector
RJ-45 Jack
RS-232 DCE
Connector
+ –
Tx/Rx
Termination
Block
Configuration
Switches
+ –
Rx
+ –
KEY
+ –
RCD
LEDON Jumper (J2)
/RST Jumper (J1)
RX Gain
Adjustment
TX Gain
Adjustment
TX Gain Jumper (J3)
Figure 1: 5902 Module Layout