Installation Instructions: Deco Grande (06810/11/12/13)

Tel +44 (0) 1924 893380

www.belllighting.co.uk

Email [email protected]

Page 1 

Testing & Commissioning for

Emergency Luminaire

Ensure the Load is connected.

Connect the battery.

Switch on the Unswitched Supply

- Check the Charge LED illuminates.

Switch on the Maintained Supply

- Check the LED illuminates as normal.

Switch off the Maintained Supply.

Switch off the Unswitched Supply

- Check the Charge LED extinguishes and the

load LED illuminates at a reduced output.

Enter the commissioning date on the Battery Pack.

Switch on the Unswitched Supply

Luminaire Ref/Location

_________________________

In Case of difficulty, contact the Installation Engineers:- 

_____________________________

Tel: __________________

Full Recharge Time 24 Hours

Duration 3 Hours

Lamp Type - LED

ROUTINE TEST RECORD

Year 1

Year 2

Year 3

Year 4

Year 5

Monthly Test

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Three Hour

Tel +44 (0) 1924 893380

www.belllighting.co.uk

Email [email protected]

Page 1 

Testing & Commissioning for

Emergency Luminaire

Ensure the Load is connected.

Connect the battery.

Switch on the Unswitched Supply

- Check the Charge LED illuminates.

Switch on the Maintained Supply

- Check the LED illuminates as normal.

Switch off the Maintained Supply.

Switch off the Unswitched Supply

- Check the Charge LED extinguishes and the

load LED illuminates at a reduced output.

Enter the commissioning date on the Battery Pack.

Switch on the Unswitched Supply

Luminaire Ref/Location

_________________________

In Case of difficulty, contact the Installation Engineers:- 

_____________________________

Tel: __________________

Full Recharge Time 24 Hours

Duration 3 Hours

Lamp Type - LED

ROUTINE TEST RECORD

Year 1

Year 2

Year 3

Year 4

Year 5

Monthly Test

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Three Hour

Date

Revision

1.6.2022

2

06810-11_12_13 Deco Grande Installation Ins.indd   4

06810-11_12_13 Deco Grande Installation Ins.indd   4

23/06/2022   09:22

23/06/2022   09:22

Содержание Deco Grande 06810

Страница 1: ...driver lead must be connected to the socket marked DC The emergency module lead must be connected to the socket marked YJD Maintained operation In this mode the luminaire is continuously on In the event of power failure the luminaire will revert to emergency mode Connections NEUTRAL to N Permanent 230V mains to PERMANENT LIVE L SWITCHED LIVE K link to PERMANENT LIVE Non maintained operation In thi...

Страница 2: ...nton West Yorkshire WF6 1TN T 44 0 1924 893380 F 44 0 1924 894320 E sales belllighting co uk www belllighting co uk Installation Instructions Deco Grande 06810 11 12 13 0 C to 35 C Date Revision 1 6 2022 2 06810 11_12_13 Deco Grande Installation Ins indd 2 06810 11_12_13 Deco Grande Installation Ins indd 2 23 06 2022 09 22 23 06 2022 09 22 ...

Страница 3: ...ns power is switched off the indicator LED immediately switches back to GREEN when mains power is switched on Notice Battery failed during test After an exchange of the battery and holding down the button 10S reset the timer the indicator LED switches to GREEN 02 Indicator LED System status is locally by a bi color indicator LED LED Indication Commentary Status Standby System OK Permanent green Ma...

Страница 4: ...r 5 Monthly Test Signed Date Signed Date Signed Date Signed Date Signed Date Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Tel 44 0 1924 893380 www belllighting co uk Email sales belllighting co uk Page 1 Check the Charge LED illuminates Switch on the Maintained Supply Check the LED illuminates as normal Switch off the Maintained Supp...

Отзывы: