background image

Installation Instructions: Deco Grande (06810/11/12/13)

Important Information 

We recommend that luminaires are installed by 
a qualified electrician ensuring the installation 
complies with current IEE wiring regulations 
BS7671:2018 & local building control.

•  All tests should be carried out in accordance to EN  
 50172:2004.
•  BELL will not accept responsibility for any claims  
  arising from a poor installation.
•  The light source of this luminaire is not replaceable:  
  when the light source reaches end of life, the  
  whole luminaire must be replaced.
•  Operating Temperature 0°C to +35°C.
•  You are advised to test 5 samples before mass  
  application of sensor in a new lighting project. The  
  distance between any inductive sensors should be  
  greater than 3m.
•  Microwave maximum operating height 3.2m

Safety

•  Before installation/maintenance, ensure that the  
  supply to the luminaire is switched of and the circuit  
  breakers or fuses are removed or switched off
•  This product is IP20 rated and not suitable for    
  external applications
•  This product is class II rated
•  This product is non-dimmable / 230V 50Hz

Read these instructions before  installation and retain for future reference

This equipment should be installed by a competent electrician

Installation:

 

•  Pull away the diffuser from the base of luminaire

•  Loosen but do not remove the 4 x lamp retaining screws

•  Adjust the position of the lamp to align the hole in the keyhole slots with the retaining screws, and 
  remove the lamp from the base

•  Unplug the driver and emergency module leads from the lamp

•  Select a suitable cable entry point already provided or by drilling into the base

•  Prepare the ceiling/mounting points and mains supply cable, ensuring the fixing surface/mechanism  
  is sufficient to support the luminaire weight.

Technical He44 (0)1924 893380

www.

belllighting

.co.uk

British Electric Lamps Ltd 

Unit A Foxbridge Way, Normanton Industrial Estate

Normanton, West Yorkshire. WF6 1TN

T

: +44 (0)1924 893380  

F

: +44 (0)1924 894320 

E

: [email protected]

www.

belllighting

.co.uk

Battery Pack

Terminal 

Block

Emergency 

Module

LED Driver

DC

YJD

Base

LED Lamp

Important

 

The LED driver lead 

must

 be connected to the  

socket marked 

DC

The

 emergency module lead 

must be connected  

to the socket marked

 YJD

Maintained operation:

   

(In this mode the luminaire is continuously on. 
In the event of power failure the luminaire will 
revert to emergency mode).

Connections:

•  NEUTRAL to (N) 
•  Permanent 230V mains to PERMANENT LIVE (L) 
•  SWITCHED LIVE (K) -link to PERMANENT LIVE

Non maintained operation 

(In this mode the luminaire can be lit and controlled by a switched live  enabling 
the luminaire to be switched on and off. In the event of power failure the 
luminaire will revert to emergency mode).

Connections: 
•  Live from the light switch to SWITCHED LIVE (K) 
•  NEUTRAL to N 
•  Permanent 230v mains to PERMANET LIVE (L) 
•  Connect the battery plug into the emergency module observing correct polarity 
•  Reconnect the LED driver lead to the socket marked DC on the lamp 
•  Reconnect the emergency module lead to the socket marked YJD on the lamp 
•  Replace the lamp by aligning the holes in the keyhole slots with the retaining  
  screws on the base, tests as this may cause damage to the electronics adjust the  
  lamp so the retaining screws now are aligned with the slots of the keyhole slots,  
  and retightened the retaining screws 
•  Set the colour temperature on LED plate 
•  Re-fit the diffuser by placing over the base and push it into the right position 
•  Reconnect the power supply and check for correct operation 
•  Luminaires fitted with an electronic ballast or LED driver are exempt from  

 

 insulation resistance tests as this may cause damage to the electronics

ON

1

2

1

2

I

ON

-

3000K

II

ON

ON

4000K

III

-

ON

5700K

ON

Maintenance:

 

This emergency luminaire can be operated in 
maintained or non-maintained mode, but when 
operated in emergency (battery back-up) mode, the 
lamp will illuminate at reduced light output. 

This product may contain substances that can be 
hazardous to the environment if not disposed of 
properly. Electrical and electronic equipment should 
never be disposed of with general household waste  
but must be separated for its correct treatment and 
recovery. Where possible recycle your packaging.

K
L

(K) Switched Live (Brown)

(L) Permanent Live (Black)
(N) Neutral (Blue)

N

Date

Revision

1.6.2022

2

06810-11_12_13 Deco Grande Installation Ins.indd   1

06810-11_12_13 Deco Grande Installation Ins.indd   1

23/06/2022   09:22

23/06/2022   09:22

Содержание Deco Grande 06810

Страница 1: ...driver lead must be connected to the socket marked DC The emergency module lead must be connected to the socket marked YJD Maintained operation In this mode the luminaire is continuously on In the event of power failure the luminaire will revert to emergency mode Connections NEUTRAL to N Permanent 230V mains to PERMANENT LIVE L SWITCHED LIVE K link to PERMANENT LIVE Non maintained operation In thi...

Страница 2: ...nton West Yorkshire WF6 1TN T 44 0 1924 893380 F 44 0 1924 894320 E sales belllighting co uk www belllighting co uk Installation Instructions Deco Grande 06810 11 12 13 0 C to 35 C Date Revision 1 6 2022 2 06810 11_12_13 Deco Grande Installation Ins indd 2 06810 11_12_13 Deco Grande Installation Ins indd 2 23 06 2022 09 22 23 06 2022 09 22 ...

Страница 3: ...ns power is switched off the indicator LED immediately switches back to GREEN when mains power is switched on Notice Battery failed during test After an exchange of the battery and holding down the button 10S reset the timer the indicator LED switches to GREEN 02 Indicator LED System status is locally by a bi color indicator LED LED Indication Commentary Status Standby System OK Permanent green Ma...

Страница 4: ...r 5 Monthly Test Signed Date Signed Date Signed Date Signed Date Signed Date Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Tel 44 0 1924 893380 www belllighting co uk Email sales belllighting co uk Page 1 Check the Charge LED illuminates Switch on the Maintained Supply Check the LED illuminates as normal Switch off the Maintained Supp...

Отзывы: