INSTRUCTIONS

APPLICATION - 

For automatically contr

olling the liquid level in

a closed tank by float movement.

MOUNTING - Scr

ew-in Tank Float Switches are mounted

directly to the tank by means of the 2

1

/

2

" I.P.S. threaded fitting

(D). Before screwing this fitting into tank, loosen Nut (C) so that
the fitting (D) is free to rotate in the switch bracket. Tighten the
fitting (D) so that there will be no leak past the threads. Then
revolve the switch case until it is horizontal and tighten Nut (C).

REVERSE ACTION - T

o change, relocate operating link to the

opposite slot in base plate and corresponding hole in adjusting
plate.

ADJUSTMENT - Switches ar

e shipped from the factory set for

a specified float travel. Reasonable adjustment of float travel
can be made in the field by moving adjusting strips (7) which
are held in place by Screws (A) and (B). Loosen Screw (B) and
moving upper adjusting strip (7) will affect the upper limit of
float travel only. Loosening Screw (A) and moving lower adjust-
ing strip (7) will affect the lower limit of float travel.

CAUTION:  Switches ar

e shipped with a bracket attached to

the mounting plate. This bracket prevents the float and the rod
from moving in the tank during shipment. When installing the
system, this clearly marked shipping bracket must be removed
and discarded.

5

INSTRUCTIONS

APPLICATION - 

Mechanical Alter

nators serve to open and

close an electric circuit by an upward and downward float
movement. The forces are applied by means of a float operat-
ing between different liquid levels. The action is such that two
switch units are alternated on successive cycles. If the liquid
level continues to rise or fall with one pump in operation, the
lever will continue to travel to a further position at which point
the  “second” switch will be operated, throwing the stand-by
pump across the line.

MOUNTING - Mechanical alter

nators are mounted directly to

the tank by means of the 2

1

/

2

" I.P.S. threaded fitting (D). Before

screwing this fitting into tank, loosen Nut (C) so that the fitting
(D) is free to rotate in the switch bracket. Tighten the fitting (D)
so that there will be no leak past the threads. Then revolve the
switch case until it is horizontal and tighten Nut (C).

ST

ANDARD OPERATION - 

Contacts ar

e arranged for sump

action. In this form the contacts will close on increase in liquid
level.

REVERSE ACTION - T

o change, relocate operating link to the

opposite slot in base plate and corresponding hole in adjusting
plate.

ADJUSTMENT - Switches ar

e shipped from the factory set for

a specified float travel. Reasonable adjustment of float travel
can be made in the field by moving adjusting strips (7) which
are held in place by Screws (A) and (B). Loosen Screw (B) and
moving upper adjusting strip (7) will affect the upper limit of
float travel only. Loosening Screw (A) and moving lower adjust-
ing strip (7) will affect the lower limit of float travel.

CAUTION:  Switches ar

e shipped with a bracket attached to

the mounting plate. This bracket prevents the float and the rod
from moving in the tank during shipment. When installing the
system, this clearly marked shipping bracket must be removed
and discarded.

T

ANK FLOAT SWITCH

MECHANICAL ALTERNATOR

Item

Number

Part

Number

Description

Required

Number

1

Complete Float Switch

1

DA0393

with Float - NEMA 1

4

Float

1

DA0165

7

7

B

A

2

5

1

C

D

4

3

7

7

B

A

2

5

1

C

D

4

3

Item

Number

Part

Number

Description

Required

Number

1

Complete Mech. Altr.

1

DA0361

with Float - NEMA 1

4

Float

1

DA0165

Содержание Hoffman Specialty SCC4

Страница 1: ...INSTRUCTION MANUAL DN0147 REVISION H Hoffman Specialty Vented Condensate Units Watchman Series WC WCS and Series SCC WCS Simplex Watchman WCS8 20B SCC4 WC Duplex Watchman WCD 12 20BMA ...

Страница 2: ......

Страница 3: ...LD BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE DASHED LINE WIRING COMPONENTS BY OTHERS MODEL SCC2 SCC3 SCC4 DUPLEX 3 PHASE UNITS WITH CONTROL PANEL CONNECTION DIAGRAM ELEMENTARY DIAGRAM LINE 1 H3 H 4 LINE TRANSFORMER FUSE TYPE FNQ R OR EQUIV 600V AMP 1 2 MAIN DISCONNECT SWITCH AND SHORT CIRCUIT PROTECTION BY OTHERS FIELD WIRING SHOULD BE IN ACCORDANCE WITH THE N E C TRANSF PRIMARY JUMPER PER TRAN...

Страница 4: ...structions could result in injury or property damage OPERATION AND MAINTENANCE Operators must be familiar with all sections of this manual to understand the operation of the unit Hot water steam and electricity can be hazardous Check motor nameplate for any lubrication requirements Pumps require no lubrication NOTICE AUTO RESTART Single phase motors will restart automatically after thermal overloa...

Страница 5: ...ues to rise or fall with one pump in operation the lever will continue to travel to a further position at which point the second switch will be operated throwing the stand by pump across the line MOUNTING Mechanical alternators are mounted directly to the tank by means of the 21 2 I P S threaded fitting D Before screwing this fitting into tank loosen Nut C so that the fitting D is free to rotate i...

Страница 6: ...faces of the seal clean of any foreign matter Moisten the carbon section of the rotating part of the seal and place onto the shaft to seat against ceramic Place seal spring onto shaft 13 Hold motor shaft as described in 4 and replace the impeller on the shaft clockwise rotation making sure it is tight 14 Orient motor for pump reassembly with conduit opening to the left When mounting pump case disc...

Страница 7: ...aring Ring 1 DP1665 7 Capscrew 4 DJ0083 8 Wear Ring 1 DP0482 9 Pipe Plug 1 4 1 P39040 10 Water Slinger 1 DP0848 Seal Kit including Mechanical Seal Head Gasket Case to 1 180013 Receiver Gasket Complete Pump and Motor Assembly 1 180001 Order Replacement Parts by Description and Part No Specify Serial No shown on nameplate 1 10 7 3 4 8 6 9 5 2 WATCHMAN B DESIGN FULL MOTOR PUMP PARTS LIST ...

Страница 8: ...th the motor vertical top end bell down and with belleville washers or finger springs properly oriented in the top end bell recess lower the rotor and head assembly as a unit holding it by rotor shaft 17 Orient the pump head properly and install the thru bolts 18 Place motor vertically with pump end up Do not attempt assembly of the head and impeller with shaft horizontal 19 The carbon rotating pa...

Страница 9: ...g Ring 1 DP1602 16 Head to Case Capscrews 3 DJ0077 17 Case to Receiver Gasket 1 DG0060 Seal Kit including Mechanical Seal Head Gasket Case to 1 180013 Receiver Gasket Complete Pump and Motor Assembly 1 180060 WATCHMAN A DESIGN PUMP AND MOTOR ASSEMBLY 15 14 12 10 16 13 11 17 1 5 2 4 8 8 6 3 9 7 12 15 14 12 12 3 1 5 10 17 16 13 11 9 8 6 7 2 4 Order Replacement Parts by Description and Part No Specif...

Страница 10: ... loose If it is hold in place with grease Using clean lint free cloth wipe mating surfaces perfectly clean Soap shaft and push seal onto shaft so that carbon will contact ceramic seal If spacer is required use grease to cause spacer to adhere to bottom of seal after seal has been put on shaft Be sure spacer is on larger diameter of shaft so that it will not catch between shoulder and impeller 13 R...

Страница 11: ... 1 DP1603 5 Wearing Ring 1 DP0482 8 Impeller Capscrew 1 DJ0213 9 Impeller Washer 1 DJ0267 10 Capscrews 8 DJ0066 16 Water Slinger 1 DP0848 Seal Kit including Mechanical 6 7 Seal Head Gasket 1 180014 Case to Receiver Gasket 1 DG0060 616PF PUMP USED ON SCC 1 10 16 3 10 6 7 9 8 4 5 2 Order Replacement Parts by Description and Part No Specify Serial No shown on nameplate 11 ...

Страница 12: ...8200 N Austin Avenue Morton Grove Illinois 60053 Phone 847 966 3700 Fax 847 965 8379 www xylem com bellgossett Bell Gossett is a trademark of Xylem Inc or one of its subsidiaries 2019 Xylem Inc DN0156H March 2019 ...

Отзывы: