INSTRUCTION MANUAL
6-71-075-110
REVISION A
The ecocirc
®
auto/vario Series Pumps
Страница 1: ...INSTRUCTION MANUAL 6 71 075 110 REVISION A The ecocirc auto vario Series Pumps ...
Страница 2: ...lectrical data The motor is protected Make certain that a properly sized circuit is available Wire size should be based on the current carrying amp capacity of the conductor The pump must be grounded in accordance with the current national and local codes Ground wire should be copper with a current capacity at least equal to that of the wire carrying power to the pump Observe all minimum code requ...
Страница 3: ...zard Adequate electrical grounding is required for the safe operation of B G Pumps Ground the pump back to the service using a copper conductor at least the size of the circuit connectors supplying the pump Connect the ground wire to the ground terminal in the wiring compartment Failure to follow these instructions could result in serious personal injury death and or property damage WARNING Risk o...
Страница 4: ...d Light No Error 1 Housing not filled with water 2 Suction piping too small 3 Total head too high 4 Impeller plugged 1 Properly prime housing 2 Increase to pump inlet size or one size larger 3 Reduce discharge head 4 Disassemble pump and clean motor separating wall and impeller Noisy pump operation Solid Light No Error 1 Air trapped in housing 2 Rotor bearing worn 3 Debris in housing 1 Check pump ...