background image

INSTALLATION INSTRUCTIONS 

(cont'd)

INSTALLATION INSTRUCTIONS 

(cont'd)

The  by-pass  valve  should  be  installed  after  the  pump  between
the supply and return piping. It can be installed either in the hor-
izontal or vertical position provided it is in accordance with the
direction  of  flow  as  indicated  by  the  arrow  on  the  valve  body
(see  Figure  1).  With  all  valves  open,  set  the  bypass  valve  to
maximum  pressure  (clockwise).  Gradually  open  the  bypass
valve  (counterclockwise)  until  flow  begins  in  the  bypass  valve.
Increase the pressure setting by 1/2 to 1 psi or turn knob clock-
wise  1/2  revolution  so  the  water  stops  flowing  through  the
bypass valve.

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

Turn  the  knob  to  the  desired  value  of  the  graduated  scale;  the
values correspond to the discharge pressure of the pump. Lock
the setscrew located on the knob.

CAUTION: Make sure that all the connecting pipework
is water tight.

CAUTION:  If  the  by-pass  valve  is  not  installed,  com-
missioned  and  maintained  properly,  according  to  the

instructions contained in this manual, it may not operate cor-
rectly and may endanger the user. 

SERVICE INSTRUCTIONS

There is no service required for the differential by-pass valve.

CAUTION:  Corrosion  or  leakage  of  the  differential  by-
pass  valve  can  cause  damage  or  injury,  Periodically

inspect the differential by-pass valve for signs of leakage or
corrosion.  If  noted,  the  differential  by-pass  valve  must  be
replaced.  Failure  to  follow  these  instructions  could  result  in
property damage and/or moderate personal injury.

CAUTION:  Overtightening  and  breakage  can  occur
with  the  use  of  Teflon

®

pipe  joint  compounds.  Teflon

®

provides lubricity so that care must be exercised not to over
tighten joints. Failure to follow these instructions could result
in property damage and/or moderate personal injury.

mH2O

1
2
3
4
5
6

mH

2

O

1
2
3
4
5
6

TYPICAL INSTALLATION

FIGURE 1

ITT
8200 N. Austin Avenue
Morton Grove, IL 60053
Phone: (847) 966-3700
Fax: (847) 966-9052
www.bellgossett.com

© Copyright © 2010 ITT Corporation
Printed in U.S.A. 12-10