Using your LCD Rack Console
5. Apply power to the LCD Rack Console. The KVM Switch will enter into
flash-upgrade mode and wait for the data to upgrade.
6. Click “Write Flash” to start the upgrade. The upgrade process takes about
six seconds. You should see “WRITE OK” display when the upgrade
completes successfully.
7. Disconnect the Serial Flash Cable,
POWER OFF
the KVM Switch, set the
DIP switch back to the Normal Run Operation position “ON, ON”, and
then power on the LCD Rack Console. The LCD Rack Console should be
running on the new firmware. The OSD will display the FW version in the
bottom-right corner of the “Main Menu” page.