UK24MOD

 

Belimo Gateway MP to Modbus RTU 

 

www.belimo.com 

T9-

UK24MOD • en • v1.7 • 02.2014 • Subject to changes 

15 / 20 

 

 

Modbus register description 

(continued)

 

Register 12: 

Actuator type 

Actuator type; the allocation may deviate from the basic category with some actuators. 

 

Actuator type 

Actuator not connected / not known 

Air/water actuators with/without safety function   

Valve actuator, linear 

Valve actuator, rotary 

Fire damper actuator 

VAV controller / EPIV 

MPL actuator 

 

Note: In the event of a communications interruption, the Gateway will discard the affected 
actuator after 10 seconds and reset the actuator type to 0. Monitoring of the actuator is thus 
accomplished preferably with this register. 

 

Register 13: 

Time monitoring 

Remaining time in seconds for the renewal of the override control (fire & smoke only). The 
counter will be set to 120 seconds with each writing access at Register 2. 

 

Register 14: 

Min / Vmin setting 

Minimum limit (position or flow) in hundredths of one percent,  
i.e. 0…10,000 corresponds to 0…100% 

Attention: Changing the limit may result in malfunction of the device.  

Register 15: 

Max / Vmax setting 

Maximum limit (position or flow) in hundredths of one percent,  
i.e. 2000…10,000 corresponds to 20…100% 

Attention: Changing the limit may result in malfunction of the device. 

Register 16: 

Absolute volumetric flow 

Absolute volumetric flow (or pressure) 

This value is available only for VAV controllers and EPIV units (Actuator Type: 5).  
For all other types, 65535 will be entered. 

The unit depends on the node type:  
[m

3

/h] for VAV controllers 

[Pa] for VAV controllers in STP mode 
[l/min] for EPIV units 

Register 17: 

Nominal volumetric flow 

Nominal volumetric flow (or pressure) 

This value is available only for VAV controllers and EPIV units (Actuator Type: 5).  
For all other types, 65535 will be entered. 

The unit depends on the node type:  
[m

3

/h] for VAV controllers 

[Pa] for VAV controllers in STP mode 
[l/min] for EPIV units 

Service register 1001 (former 161): 

Modbus baud rate 

 
 
 

Modbus baud rate (=x*100) in accordance with the setting of the DIP switches, 
i.e. 96 

 9600 Baud 

 

Service register 1002 (former 162): 

Modbus address 

Modbus address (1..247) in accordance with the setting of the DIP switches 

 

Service register 1003 (former 163): 

Response delay 

Response delay (2…100 ms); the default value is 2 ms; the response delay is set to a fixed 4 
ms with a baud rate of 9600. 

The response delay must be increased in the event that the Modbus Master is unable to switch 
quickly enough from transmission to reception mode. 

 

Service register 1004 (former 164): 

Firmware Version 

Firmware Version of the device 

 

Содержание UK24MOD

Страница 1: ...Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical installation 5 Dimensions 7 Operation elements 8 Operation behaviour 8 Modbus register overview 11 Modbu...

Страница 2: ...014 Subject to changes www belimo com Complete overview Gateway MP Modbus RTU Suitable MP MPL MFT 2 Actuators Damper actuators Fire damper actuators VAV actuators Actuators for characterised control v...

Страница 3: ...ax 8 pcs Communication with actuators Belimo MP Bus Master Slave 1200 Bd Maximum signal conductor lengths MP Dependent on the number of connected actuators actuator type type of supply and signal cond...

Страница 4: ...tuator This can be a passive resistance sensor PT1000 NI1000 or NTC an active sensor output DC 0 10 V or a switching contact This provides a straightforward way of digitising the analogue signal of th...

Страница 5: ...RS485 line is galvanically isolated from the MP Bus GND Connection of the MP Bus The network consists of a 3 pin connection MP communication and 24 V supply Possibility of connecting a maximum of 8 M...

Страница 6: ...24A MP Total power rating 5 5 VA 6 VA 5 VA 5 VA 21 5 VA With local supply AC 24 V on site Maximum signal conductor length Wire mm L max cable length m 0 75 800 1 00 1 50 2 50 The signal conductor leng...

Страница 7: ...he mass of curves For cables with wire mm Cable length m 0 75 55 1 00 75 1 50 110 2 50 190 The power consumption W of the MP MPL MFT 2 actuators used is to be added and the corresponding signal conduc...

Страница 8: ...ration behaviour Setting the Modbus address The Modbus address is set in binary form with the 8 DIP switches under the front cover The valid address range is 1 247 Values outside of this range will be...

Страница 9: ...us ends with one resistor each A suitable 150 element is present in the Gateway which can be switched with DIP switch 1 on the base plate The RS485 line can be polarised with two resistors DIP switche...

Страница 10: ...shed preferably with the Actuator type register 12 Addressing MP actuators The Gateway supports the assigning of addresses to the MP nodes by means of the keys UP OK and DOWN located behind the front...

Страница 11: ...Override control MP n 3 Command MP n 4 Actual position MP n 5 Relative volumetric flow MP n 6 Errors Malfunctions MP n 7 Sensor type MP n 8 Current sensor value MP n 9 Series number 1st part MP n 10...

Страница 12: ...register overview continued Service register Note Devices with V1 06 and older use registers register 161 164 for service information Register Number High Byte Low Byte 1001 Modbus baud rate 1002 Modb...

Страница 13: ...so be repeated within 120 seconds recommendation 90 sec If the override command is not renewed then the Gateway will move the actuator into safety position and signal an error see Register 6 The remai...

Страница 14: ...ts can be reset with Register 3 command 4 or with the Belimo PC Tool Malfunctions 0 and 4 cannot be reset The error bits will be reset automatically by the Gateway Register 7 Sensor type Note Switchin...

Страница 15: ...0 000 corresponds to 20 100 Attention Changing the limit may result in malfunction of the device Register 16 Absolute volumetric flow Absolute volumetric flow or pressure This value is available only...

Страница 16: ...an be obtained through the Internet www belimo eu Products Download Center Connecting the PC Tool for parameterisation of the MP MFT 2 actuators The MP network can be scanned actuators can be addresse...

Страница 17: ...ty Service information can be found in registers 1001 to 1004 former 161 to 164 Known issues Modbus telegrams longer than 20 Bytes e g ReadHoldingRegister with more than 8 registers cause wrong regist...

Страница 18: ...UK24MOD Belimo Gateway MP to Modbus RTU 18 20 T9 UK24MOD en v1 7 02 2014 Subject to changes www belimo com...

Страница 19: ...UK24MOD Belimo Gateway MP to Modbus RTU www belimo com T9 UK24MOD en v1 7 02 2014 Subject to changes 19 20...

Страница 20: ......

Отзывы: