Operation 

(continued) 

Setting the BACnet baud rate 

 

 

 

 

 

 

 

 

 

 

 

The BACnet baud rate is set using the DIP switches under the front cover to the values 9'600, 
19'200, 38'400 and 76'800. 

 

 

The RS485 line must be completed at both bus ends with one resistor each. A suitable 120 

 

element is present in the Gateway which can be switched with DIP switch 1 on the base plate. 

  

 

The RS485 line can be polarised with two resistors (DIP switches 2 and 3) in order to reduce 
interference effects during communications pauses. The biasing is implemented as a rule at one 
of the bus ends. Switches 2 and 3 must always be respectively activated or deactivated 
together. 

Important: 
The generally valid guidelines for BACnet MS/TP (RS485) are to be observed! 

Firmware Upgrade 

 

If required, the firmware of the gateway can be upgraded via USB link. The required Upgrade 
Tool can be obtained from Belimo. 
 
Procedure: 
1. Disconnect power supply from device 
2. Set DIP switch 4 "Programming" to ON 
3. Connect the device with the notebook via USB 
4. Download of firmware according to special instruction 
5. Remove USB cable 
6. Set DIP switch 4 "Programming" to OFF 
7. Connect power supply to device 

 

Содержание UK24BAC

Страница 1: ...Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical installation 5 Dimensions 7 Operation 8 Protocol Implementation Conformance Statemen...

Страница 2: ...Subject to changes www belimo com Complete overview Gateway MP BACnet MS TP Suitable MP MPL MFT 2 Actuators Damper actuators Fire damper actuators VAV actuators Actuators for characterised control va...

Страница 3: ...Supported actuators MP MPL MFT 2 BF TopLine Quantity of actuators max 8 pcs Communication with actuators Belimo MP Bus Master Slave 1200 Bd Maximum signal conductor lengths MP Dependent on the number...

Страница 4: ...logue signal of the sensors with the Belimo actuator and transferring it via UK24BAC to the BACnet MPL actuators don t provide a sensor input Installation and commissioning Installation and wiring The...

Страница 5: ...aration shall be provided for segments crossing buildings Connection of the MP Bus The network consists of a 3 pin connection MP communication and 24 V supply Possibility of connecting a maximum of 8...

Страница 6: ...ite Maximum signal conductor length Wire mm L max cable length m 0 75 800 1 00 1 50 2 50 The signal conductor lengths can be significantly increased if the actuators are supplied with AC 24 V locally...

Страница 7: ...the mass of curves For cables with wire mm Cable length m 0 75 55 1 00 75 1 50 110 2 50 190 The power consumption W of the MP MPL MFT 2 actuators used is to be added and the corresponding signal condu...

Страница 8: ...tting the BACnet MAC address The BACnet MAC address is set in binary form with the 7 DIP switches under the front cover The valid address range is 1 127 Values outside of this range will be interprete...

Страница 9: ...2 and 3 in order to reduce interference effects during communications pauses The biasing is implemented as a rule at one of the bus ends Switches 2 and 3 must always be respectively activated or deac...

Страница 10: ...Gateway supports the assigning of addresses to the MP nodes by means of the keys UP OK and DOWN located behind the front cover Procedure 1 Press down the OK key and keep it down approx 2 s until LED1...

Страница 11: ...orted Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Data Sharing WritePropertyMultiple B DS WPM B Data Sharing COV Unsolicited B...

Страница 12: ...AV n 100 2 Nominal volumetric flow AV n 100 3 Object processing 1 Present_Value writeable for OVERRIDE_ n and COV_MODE 2 Present_Value writable for MIN_STPT_ n und MAX_STPT_ n 3 Only if object comman...

Страница 13: ...scard the affected actuator after 10 seconds and reset the actuator type to 0 Monitoring of the actuator is thus accomplished preferably with this object Each MP node has an unambiguous series number...

Страница 14: ...for EPIV units 0 65535 SNS_TYPE_ n Multi state Value n 100 3 Sensor type connected to the actuator in the absence of sensor specification the wiring at the Y input of the MP actuator will have the ef...

Страница 15: ...tion of the device 20 100 NOM_FLOW_ n Analog Value n 100 3 Nominal volumetric flow or pressure The unit depends on the node type m3 h for VAV controllers Pa for VAV controller in STP mode l min for EP...

Страница 16: ...ddressing function reworked Known issues Firmware V1 07 New functions modifications WritePropertyMultiple service supported Feedback values are rounded Unconfirmed COV Notification for Multi state Val...

Страница 17: ...UK24BAC Belimo Gateway MP to BACnet MS TP www belimo com T9 UK24BAC en v1 9 06 2018 Subject to changes 17 20...

Страница 18: ...UK24BAC Belimo Gateway MP to BACnet MS TP 18 20 T9 UK24BAC en v1 9 06 2018 Subject to changes www belimo com...

Страница 19: ...UK24BAC Belimo Gateway MP to BACnet MS TP www belimo com T9 UK24BAC en v1 9 06 2018 Subject to changes 19 20...

Страница 20: ......

Отзывы: