1. Enter setup menu

Switch the unit to ‘standby’ mode, press and hold “     ”, then press“ - ” , hold “ - ” and release “    ”, keep 
holding “ - ” for 10s until “ 

S-F

 ” appears.

2. Select sub-menu “ 

S-F

 ” or “ 

S-P

 ” After enter setup menu and “ 

S-F

 ” appears, press “ + “ or “ - ” to select “ 

S-F

 ” or “ 

S-P 

”, confirm by “    ”.

3. Select function under sub-menu

Under sub-menu, press “     ” key momentarily to select the functions sequentially. 

4. Adjust parameters

Press “ + ” or “ - ” to adjust parameter value.

5. Save changes and

go back to sub-menu selection

Press and hold “     ” , then press“ + ” , hold “ + ” and release “     ”, keep holding “ + ” for 1s.

Under sub-menu, press “      ” to exit.

6. Exit setup menu
7. Time out

If there is no key operation for 30 seconds, new setting will not be stored and exit automatically.

V1.5  04. 2014 · Subject to modification

2

T24-DM1 LCD Temperature Controller

Setup menu

Jumper setting

Wiring diagrams

Notes

Caution

Sub-menu 

S-F

Firmware version
Temperature display
Selection for unoccupancy mode
Display selection

Restore factory setting

S
t
uA
c

rF

Display only
Display in °C only
To select 

uA1

 or 

uA2

cAt

 = display ambient temperature

cSP

 = display setpoint value

rFC

 = current setting

rFS

 = restore factory setting 

(factory default 

uA1

)

(factory default 

cAt

)

(factory default 

rFC

)

Sub-menu 

S-P

Proportional band
Integral time
Upper setpoint limit
Lower setpoint limit

 

Unoccupancy setpoint range - cool

 

Unoccupancy setpoint range - heat

 

Display offset

A
I
U
L
C
H
n

Adjustable, 1...10K
Adjustable, 0...30 (1=10s)
Adjustable, 9...40°C
Adjustable, 5...36°C
Adjustable, 5...40°C
Adjustable, 5...36°C
Adjustable, -2,-1,0,+1,+2

 

(factory default 5K)
(factory default 6)
(factory default 40°C)
(factory default 5°C)
(factory default 26°C)
(factory default 16°C)
(factory default 0)

Open

Close

Use external sensor

Use built-in sensor (factory default)

Open
Close

DC 0...10V output
DC 2...10V output (factory default)

Terminals for sensor

4

3

2

1

  Valve actuator

A C   24V

C om

0-10V

2

1

3

T24-DM1

Feedback

5

5

*2 & 4 are internally shorted

SR1

GND

OCU

External
sensor

Occupancy 
contact

- 22 or 24 AWG twisted shielded pair double insulated cable is recommended as sensor cable and its length must not exceed 25m.
- Do not bundle and run power cable and sensor cable in the same conduit.
- When using external sensor, run the cable away from any electric motor or power cable.
- Remove JP1 whenever using external sensor.
- Unoccupancy contact CLOSE activates unoccupancy mode.

- Unit to be opened by accredited servicing agents only.
- Electronic control - Type 2.B action (micro-disconnection operation).
- Separate collection for electrical and electronic equipment.